Worked example · CALC-012
How to Use the Cantilever Masonry Retaining Wall Calculator: Worked Example
A step-by-step worked example of the Cantilever Masonry Retaining Wall calculator, with a screen-recorded video - a reinforced concrete block retaining wall with two retained heights, from Project Settings to the accepted calculation and its documents.
- Author
- ArchiSuite
- Technical review:
- Michael Sheridan
- Reviewed:
- Published:
On this page
This worked example takes one real design through the Cantilever Masonry Retaining Wall calculator, from Project Settings to an accepted calculation in Project Outputs and the documents it produces. The calculator designs a reinforced concrete block wall that cantilevers from a strip footing: for each retained height it chooses the wall thickness and reinforcement, sizes the toe or heel of the footing, and designs a shear key where sliding needs one. Every value below was entered in ArchiSuite, and every result was read from it.
Video tutorial#
The example project#
A reinforced concrete block retaining wall on a strip footing, with level ground behind it. The ground steps along the wall, so it is designed for two retained heights: 1.2 m and 1.8 m. The example takes wall case 3 (a retaining wall supporting a foundation) and a uniform surcharge of 5 kPa on the ground behind the wall, with the soil values from the project's geotechnical report.
What the example assumes:
The wall retains soil only, with a uniform surcharge on the level ground behind it. There is no building, driveway or other load on top of the wall itself.
The two heights are the highest point of each length of wall: each is designed on its own, with the same soil, footing type and wall case.
The soil values come from a geotechnical report. The report in this example is fictional; a real retaining wall needs the real report for its site.
The values are an illustration. They are not defaults for your project.
Step 1: Check the project information#
A retaining wall cannot be analysed until the project's geotechnical information is complete. In the active project's Project Settings, the example uses:
| Project Setting | Value used | Unit | Why it matters here |
|---|---|---|---|
| Earthquake Zone | 2 | Used for the earthquake load case on the wall. | |
| Soil Class | C | The site subsoil class, also used for the earthquake load case. | |
| Geotechnical report details | Demo Geotechnical Ltd, WE-GEO-003 Rev 0 | Company, report reference, title and date. A retaining wall cannot be analysed until all four are filled in with real details (placeholders such as TBC are refused). The report here is fictional, for the example. | |
| Backfill and founding soil properties | φ 30°, γ 18 | kN/m³ | The four soil properties from the report. The form's soil inputs are checked against them. |
Select Retaining walls under What are you designing? in Project Settings: the form then shows the fields retaining walls need and the Geotechnical Properties section becomes required. This calculator takes its bearing capacity from its own form, not from Project Settings.
Step 2: Open the calculator#
Make the project active. Its name is shown under Active project at the top of every page.
Click All Calculators in the sidebar.
Under Retaining Walls, choose Cantilever Masonry Retaining Wall.
Click Add Calculation, or New Calculation once the project has one.
Step 3: Enter the wall design inputs#
The form has four sections. The diagram above it shows the wall, footing, toe, heel and shear key that the inputs describe.
These are the exact values entered in the recording:
| Section | Field | Value used | Unit | What it means |
|---|---|---|---|---|
| General Info | Calculation Name | RW1 - Block retaining wall | - | Names the calculation in Project Outputs and on the drawings and calculations. |
| Retained Heights (A) | Height 1 | 1200 | mm | The first retained height: from the top of the footing to the finished ground behind the wall. Up to 3000 mm. |
| Retained Heights (A) | Height 2 | 1800 | mm | A second height, added with Add Height, where the ground steps along the wall. Each height is designed on its own, with the same soil, footing type and wall case. Up to five heights. |
| Wall & Footing Parameters | Footing type to solve | Toe | - | Which side of the wall the calculator lengthens until the wall is stable. Toe sizes the projection in front of the wall. |
| Wall & Footing Parameters | Wall case | Case 3 | - | The wall's situation from NZGS / MBIE Module 6, Figure 4.1, used for the earthquake design: Case 3 is a retaining wall supporting a foundation. Choose your own wall's case; Cases 1 and 2 are outside this calculator. |
| Wall & Footing Parameters | Geotechnical ultimate bearing capacity, qu | 300 | kPa | The founding soil's ultimate bearing capacity, entered on this form (150 to 300 kPa), from your geotechnical report. |
| Wall & Footing Parameters | Do you want a heel as well? | No | - | With a toe footing: No keeps the heel at zero while the toe is sized. |
| Geotechnical & Soil Parameters | Backfill soil friction angle, φb | 30 | ° | The retained (backfill) soil's friction angle, from the geotechnical report. Matches Project Settings, so the form does not ask you to check it. |
| Geotechnical & Soil Parameters | Founding soil friction angle, φf | 30 | ° | The friction angle of the soil under the footing. |
| Geotechnical & Soil Parameters | Backfill slope | 0 | ° | The slope of the ground behind the wall: level here (0 to 20°). |
| Geotechnical & Soil Parameters | Backfill soil unit weight, γb | 18 | kN/m³ | The backfill soil's unit weight. |
| Geotechnical & Soil Parameters | Founding soil unit weight, γf | 18 | kN/m³ | The founding soil's unit weight. |
| Geotechnical & Soil Parameters | Surcharge | 5 | kPa | A uniform load on the ground behind the wall (0 to 12 kPa). 5 kPa is this example's assumption; use the loads on your own site. |
A few points from the recording:
Height 2 is added with Add Height. Use it where the ground steps along the wall, rather than designing the whole wall for the highest point. Up to five heights can be designed in one calculation.
No Wall case is selected when the form opens. Choose your own wall's case: the (i) beside the field shows the cases from Module 6 (NZGS / MBIE), Figure 4.1.
The bearing capacity is entered on this form, not taken from Project Settings.
The soil values match Project Settings, so Analyse Data goes straight on. Had any differed, Check geotechnical values would open first, asking you to review them or continue.
Step 4: Run the calculation#
Click Analyse Data. ArchiSuite first reads the latest saved Project Settings and checks the geotechnical information, then designs each height. The Summary table appears below the form, with one row per height. If an input is out of range, the form says so beside the field and does not submit.
Step 5: Understand the results#
The Summary#
These are the values ArchiSuite showed for this example:
| Case | Hr (mm) | tw (mm) | tf (mm) | tl (mm) | hl (mm) | Total (mm) | Key | Status |
|---|---|---|---|---|---|---|---|---|
| H1 | 1200 mm | 190 mm | 300 mm | 950 mm | 0 mm | 1140 mm | 300 x 300 mm, HD12 @ 200 | Pass |
| H2 | 1800 mm | 190 mm | 300 mm | 1450 mm | 0 mm | 1640 mm | 300 x 600 mm, HD12 @ 200 | Pass |
What the columns mean:
Hr (mm) is the retained height.
tw (mm) is the wall thickness the calculator chose: a 190 mm block wall is tried first, then 240 mm.
tf (mm) is the footing thickness.
tl (mm) and hl (mm) are the toe and heel lengths. This example solves for the toe with no heel, so the heel is 0 mm and the toe grows with the height.
Total (mm) is the full footing length: toe + wall + heel.
Key is the shear key under the footing and its reinforcement. Both heights need one here.
Status must show Pass on every row you intend to build.
Reinforcement#
The Summary does not show the wall's reinforcement: it is in the Structural Calculations and on the drawings. For this example the calculations give HD12 @ 600 vertical bars for wall H1 and HD12 @ 400 for wall H2, with HD12 @ 600 horizontal bars in both, as in their summary table:
"H1 1.2 190 HD12 @ 600 HD12 @ 600 300 950 0 300 × 300 HD12 @ 200"
"H2 1.8 190 HD12 @ 400 HD12 @ 600 300 1450 0 300 × 600 HD12 @ 200"
Strength and stability checks#
The Structural Calculations document lists the governing checks for each wall. Utilisation is demand ÷ capacity or limit; 1.00 or less passes.
| Part | Check | Demand | Capacity or limit | Utilisation |
|---|---|---|---|---|
| H1 | Wall flexure | 3.68 kNm/m | 8.76 kNm/m | 0.42 |
| H1 | Bearing | 19.55 kPa | 150.0 kPa | 0.13 |
| H1 | Sliding – governs | 11.63 kN/m | 11.66 kN/m | 1.00 |
| H1 | Shear key flexure | 1.21 kNm/m | 51.03 kNm/m | 0.02 |
| H1 | Shear key shear | 7.29 kN/m | 78.69 kN/m | 0.09 |
| H2 | Wall flexure | 11.18 kNm/m | 12.86 kNm/m | 0.87 |
| H2 | Bearing | 25.59 kPa | 150.0 kPa | 0.17 |
| H2 | Sliding – governs | 21.03 kN/m | 21.33 kN/m | 0.99 |
| H2 | Shear key flexure | 6.80 kNm/m | 51.03 kNm/m | 0.13 |
| H2 | Shear key shear | 19.44 kN/m | 78.69 kN/m | 0.25 |
The document's conclusion:
What the checks show for this wall:
Sliding governs both heights (1.00 at H1 and 0.99 at H2). The calculator lengthens the toe and adds the shear key until the wall just stops sliding, so a sliding utilisation close to 1.00 is the expected result of the sizing, not a warning.
Wall flexure is the block wall bending as a cantilever. At H2 it is 0.87, which is why the taller wall has the closer vertical bars.
Bearing is low (0.13 and 0.17): the bearing limit of 150.0 kPa is the 300 kPa ultimate capacity times the calculation's bearing capacity factor, and the long toe spreads the load well.
Step 6: Accept and access the documentation#
Check that every row shows Pass, then click Accept in the Summary header. ArchiSuite shows:
Open Project Outputs from the sidebar. The calculation is listed under Accepted calculator outputs included with its status.
What you can see and download, and when:
On screen. The Summary, with every height's sizes and status, is in the calculator itself as soon as you analyse.
The document packs. Project Outputs offers three PDFs: the Project Summary, the Structural Calculations (the design basis, the earth pressures and every check for each wall) and the Structural Drawings. They download once every accepted output is paid.
Documents that wait for review. Where an Engineering Review is included (it always is for an account without a Licensed Building Practitioner number), the downloads also wait until ArchiSuite has reviewed the documents and released them for issue. See Pay and download your documents.
Once the review is released, the panel says so and every download opens.
The video ends with a quick look through the documents this example produced, as issued: the Project Summary; the PS1 Producer Statement - Design and its Schedule, shown unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; every page of the Structural Calculations; and every sheet of the Structural Drawings. The typical section at the front of the calculations also shows what the wall needs behind it: "Free-draining backfill in geotextile" and a "Perforated drain".
Common mistakes#
Incomplete geotechnical information. Geotechnical information required opens and nothing is analysed. Complete every field of Geotechnical Properties in Project Settings, click Update Project, and analyse again. See Project settings missing.
Soil inputs that differ from the report. Check geotechnical values opens. Click Review inputs to correct them, or Continue only if the different values are intended.
No wall case. No case is selected at first, and Analyse Data is refused until you choose one. Cases 1 and 2 (a wall integral to, or supporting, a building) are outside this calculator.
Designing every length for the highest point. Add a height for each step in the ground instead: each is sized on its own.
A height that fails. The calculator could not find a wall, footing and shear key that pass. Only heights that pass are drawn. See When no calculator fits.
The same name twice. Each calculation in a project needs its own name. Change the Calculation Name.
Related guides#
Cantilever Masonry Retaining Wall: every input, result and refusal of this calculator.
Open the calculator from All Calculators → Retaining Walls (signed in).
The inputs explained: Retained height, Footing type to solve, Wall case, Geotechnical Ultimate Bearing Capacity, Backfill soil friction angle, Founding soil friction angle, Backfill slope and Soil unit weight.
The other retaining walls: Timber Pole Retaining Wall and Masonry Foundation Wall.
Project Settings, Check and accept results and Pay and download your documents.
Engineering note#
Recorded with CALC-012 Cantilever Masonry Retaining Wall version 2.8.0 on 2026-11-24.
Video transcript#
0:07 The project Worked Example - Block Retaining Wall is active. In Project Settings, Retaining walls is selected, the Earthquake Zone is 2 and the Soil Class is C, and the Geotechnical Properties are complete: the report details and the backfill and founding soil properties, φ 30 degrees and 18 kN/m³.
0:23 Under All Calculators, in Retaining Walls, open Cantilever Masonry Retaining Wall, then Add Calculation. It designs a reinforced concrete block wall cantilevering from a strip footing, for up to five retained heights.
0:33 The calculation is named RW1 - Block retaining wall. Height 1 is 1200 mm; Add Height adds Height 2, 1800 mm. Each retained height runs from the top of the footing to the finished ground behind the wall, and each is designed on its own.
0:47 In Wall & Footing Parameters, the footing type to solve is Toe, with no heel; the wall case is Case 3, a retaining wall supporting a foundation; and the geotechnical ultimate bearing capacity is 300 kPa.
1:02 In Geotechnical & Soil Parameters, the backfill and founding soils are both φ 30 degrees and 18 kN/m³, as in Project Settings, the backfill slope is 0 degrees and the surcharge is 5 kPa.
1:20 Analyse Data runs the calculation. When it finishes, the Summary shows one row for each retained height.
1:27 Both heights pass. For each one the calculator chose the wall thickness tw, sized the toe tl with no heel, gives the footing thickness tf and the total footing length, and designed a shear key with its reinforcement where sliding needs one. The vertical reinforcement for each wall is in the calculations and on the drawings.
1:46 Accept adds the calculation to Project Outputs.
1:51 Project Outputs lists RW1 - Block retaining wall as an accepted output. The Structural Calculations and Structural Drawings, with the full checks and the foundation details, download from here once the outputs are paid and, where Engineering Review is included, reviewed and released. Prices are hidden in this video.
2:04 After payment and Engineering Review (not shown), Project Outputs shows the document packs ready to download. A quick look through what they contain: the Project Summary, with the project and every accepted calculation; the PS1 Producer Statement - Design and its Schedule, shown here unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; the Structural Calculations; and the Structural Drawings.