Calculator guide · CALC-012
Cantilever Masonry Retaining Wall
Design a reinforced concrete block cantilever retaining wall on a strip footing for up to five retained heights, with the toe, heel and shear key sized for you.
Video: a worked example
On this page
The Cantilever Masonry Retaining Wall calculator designs a reinforced concrete block retaining wall that cantilevers from a strip footing. It covers up to five retained heights in one calculation. For each height it chooses the wall thickness and vertical reinforcement, sizes the toe or heel of the footing, and designs the shear key and its reinforcement where sliding needs one.
Cantilever Masonry Retaining Wall · CALC-012
One calculation covers up to five wall heights, with footing layouts extending in front, behind, or both.
Use it when
- Retained heights up to 3.0 m.
- Backfill slopes up to 20°; level ground in front.
- Uniform surcharge up to 12 kPa.
Results
- Block thickness and vertical reinforcement.
- Toe and heel dimensions.
- Shear-key size and reinforcement where required.
Limits
- Not for walls that form part of a building or directly support one.
- No concentrated loads near the wall or loads on top of it.
- Drained walls only; groundwater pressure is not included.
Before you start#
This calculator reads these values from the active project's Project Settings:
Earthquake Zone and Soil Class. These are used for the earthquake load case. If either one is blank or not a supported value, the calculation is refused.
The Geotechnical Properties section. Fill in all four report details (Geotechnical Engineering Company Name, Report Reference / Revision, Report Title, Report Date) and all four soil properties (Backfill soil friction angle, φb, Backfill soil unit weight, γb, Founding soil friction angle, φf, Founding soil unit weight, γf). Save with Update Project. A retaining wall cannot be analysed until every one of these is filled in.
You enter the geotechnical ultimate bearing capacity on this calculator's own form. It does not use the project's Geotechnical Ultimate Bearing Capacity. If the two values differ, a note under the field shows both, so you can check the one you entered.
Have these ready from the site and the geotechnical report:
Each retained height you want designed, in mm (up to five).
Whether the footing can project in front of the wall (toe), behind it (heel), or both.
The backfill soil's friction angle and unit weight, the founding soil's friction angle and unit weight, and the geotechnical ultimate bearing capacity.
The backfill slope behind the wall, any uniform surcharge, and the wall case.
Step by step#
In the sidebar, click All Calculators. Choose the Retaining Walls tab, then the Cantilever Masonry Retaining Wall card.
On the Project Calculations page, click New Calculation. If there are no calculations yet, click Add Calculation.
In General Info, enter a Calculation Name (for example
MBRW 1).In Retained Heights (A), enter Height 1 in mm. Click Add Height to add more, up to five. Use the bin icon to remove a height.
In Wall & Footing Parameters:
choose Footing type to solve: Toe or Heel
choose the Wall case that describes the wall's situation (no case is selected at first, and Analyse Data is refused until you choose one)
enter the Geotechnical ultimate bearing capacity, qu
if you chose Toe, answer Do you want a heel as well?. If you choose Yes, enter the Heel length in mm.
In Geotechnical & Soil Parameters, enter Backfill soil friction angle, φb, Founding soil friction angle, φf, Backfill slope, Backfill soil unit weight, γb, Founding soil unit weight, γf and Surcharge.
Click Analyse Data. ArchiSuite first reads the latest saved Project Settings:
If the geotechnical information is incomplete, Geotechnical information required opens and nothing is analysed. Click Close, complete Project Settings, then come back and click Analyse Data again. Your form values are kept.
If your soil inputs differ from the project's soil properties, Check geotechnical values opens. Click Review inputs to go back and change them. Or click Continue to analyse with the values exactly as you entered them.
The Summary table appears below the form, with one row per height. Check that every row shows Pass.
Click Accept. You will see "Calculation accepted successfully!", the button changes to Accepted, and the calculation is added to Project Outputs.
To change a saved calculation, open it from the list. Edit the inputs and click Update Analysis.
The inputs#
Retained Heights (A). Each height is the retained height from the top of the footing to the finished ground behind the wall, in mm. Each height is designed on its own, with the same soil, footing type and wall case.
Wall & Footing Parameters. Footing type to solve decides which side of the wall the calculator lengthens until the wall is stable. Toe sizes the projection in front of the wall. Heel sizes the projection behind the wall and sets the toe to zero. With Toe, answering Yes to Do you want a heel as well? keeps the heel length you enter while the toe is sized. Click the (i) beside Footing type to solve to see drawings of the Heel footing and Toe footing arrangements. The Wall case offers Cases 3 to 6. Its (i) shows the six cases of Figure 4.1 from Module 6 (NZGS / MBIE): Case 1, retaining wall integral to building; Case 2, retaining wall supporting building; Case 3, retaining wall supporting foundation; Case 4, retaining wall protecting building up-slope; Case 5, retaining wall facilitating access and services to building; Case 6, other situations where H* > 3 m. The drawer notes that Cases 1 and 2 are outside this calculator's scope. Geotechnical ultimate bearing capacity, qu is the geotechnical ultimate bearing capacity of the founding soil, from 150 to 300 kPa.
Geotechnical & Soil Parameters. The calculator uses two soils:
The backfill soil, retained behind the wall. Backfill soil friction angle, φb and Backfill soil unit weight, γb set the earth pressure on the wall, in the static and earthquake load cases, and the weight of soil over the heel.
The founding soil, under the footing. Founding soil friction angle, φf and Founding soil unit weight, γf set the passive resistance in front of the toe and at the shear key, and the friction under the footing.
There is no base friction angle input: the calculator takes the friction between the footing and the soil as δb = φf. Backfill slope is the slope of the ground behind the wall, from 0° to 20°. Surcharge is a uniform load on the ground behind the wall, from 0 to 12 kPa.
| Input | Accepted values | Required |
|---|---|---|
| Footing type to solve | toe · heel | No |
| Soil friction angle (ϕ)(°) | As shown on the form | Yes |
| Backfill slope (ϕ)(°) | As shown on the form | Yes |
| Soil unit weight (kN/m³) | 14 to 20If not: “Maximum value is 20 kN/m³” | Yes |
| Surcharge (kPa) | As shown on the form | Yes |
| Wall case | 3 to 6If not: “Wall case must be one of 3, 4, 5, or 6.” | Yes |
| Height 1 | more than 0 and up to 3000 mmIf not: “Must be ≤ 3000 mm” | Yes |
| Height 2 | more than 0 and up to 3000 mmIf not: “Must be ≤ 3000 mm” | No |
| Height 3 | more than 0 and up to 3000 mmIf not: “Must be ≤ 3000 mm” | No |
| Height 4 | more than 0 and up to 3000 mmIf not: “Must be ≤ 3000 mm” | No |
| Height 5 | more than 0 and up to 3000 mmIf not: “Must be ≤ 3000 mm” | No |
| Do you want a heel as well? / Heel length (mm)(mm) | As shown on the form | No |
| Ultimate bearing capacity (kPa) | 150 to 300 kPaIf not: “Maximum value is 300 kPa” | Yes |
| Founding soil friction angle, φf(°) | As shown on the form | No |
| Founding soil unit weight, γf | 14 to 20 kN/m³If not: “Maximum value is 20 kN/m³” | No |
- Footing type to solveOptional
toe · heel
- Soil friction angle (ϕ)Required
°
- Backfill slope (ϕ)Required
°
- Soil unit weight (kN/m³)Required
14 to 20
If not: “Maximum value is 20 kN/m³”
- Surcharge (kPa)Required
As shown on the form
- Wall caseRequired
3 to 6
If not: “Wall case must be one of 3, 4, 5, or 6.”
- Height 1Required
more than 0 and up to 3000 mm
If not: “Must be ≤ 3000 mm”
- Height 2Optional
more than 0 and up to 3000 mm
If not: “Must be ≤ 3000 mm”
- Height 3Optional
more than 0 and up to 3000 mm
If not: “Must be ≤ 3000 mm”
- Height 4Optional
more than 0 and up to 3000 mm
If not: “Must be ≤ 3000 mm”
- Height 5Optional
more than 0 and up to 3000 mm
If not: “Must be ≤ 3000 mm”
- Do you want a heel as well? / Heel length (mm)Optional
mm
- Ultimate bearing capacity (kPa)Required
150 to 300 kPa
If not: “Maximum value is 300 kPa”
- Founding soil friction angle, φfOptional
°
- Founding soil unit weight, γfOptional
14 to 20 kN/m³
If not: “Maximum value is 20 kN/m³”
Read from Cantilever Masonry Retaining Wall (CALC-012, version 2.8.0) as it runs today. The form may also show its own limit beside an input.
Worked example#
This is a representative example taken from ArchiSuite's own tests. It is not a design for your site.
Project Settings: Earthquake Zone 2 and Soil Class C. The geotechnical report details are complete, with the backfill and founding soil both at φ 30° and γ 18 kN/m³.
Inputs: Height 1 1000, Height 2 2000, Height 3 3000 mm; Footing type to solve Toe; Do you want a heel as well? No; Wall case Case 3; Geotechnical ultimate bearing capacity, qu 300 kPa; Backfill soil friction angle, φb 30°; Founding soil friction angle, φf 30°; Backfill slope 0°; Backfill soil unit weight, γb 18 kN/m³; Founding soil unit weight, γf 18 kN/m³; Surcharge 5 kPa.
The Summary shows all three heights as Pass:
| Case | Hr (mm) | tw (mm) | tl (mm) | hl (mm) | Total (mm) | Key | Status |
|---|---|---|---|---|---|---|---|
| H1 | 1000 mm | 190 mm | 800 mm | 0 mm | 990 mm | 300 x 300 mm, HD12 @ 200 | Pass |
| H2 | 2000 mm | 190 mm | 1600 mm | 0 mm | 1790 mm | 300 x 700 mm, HD12 @ 200 | Pass |
| H3 | 3000 mm | 240 mm | 2400 mm | 0 mm | 2640 mm | 300 x 1150 mm, HD12 @ 200 | Pass |
Each passing row shows tf (mm) as 300 mm.
Results#
The Summary table has one row per height:
Case: H1 to H5.
Hr (mm): the retained height.
tw (mm): the wall thickness. The calculator tries a 190 mm wall first, then 240 mm.
tf (mm): the footing thickness.
tl (mm) and hl (mm): the toe and heel lengths.
Total (mm): the total footing length (toe + wall + heel).
Key: "None", or the shear key size and its reinforcement where one is needed (for example
300 x 300 mm, HD12 @ 200).Status: Pass or Fail. A height that fails shows "-" instead of sizes.
The vertical reinforcement for each wall is given in the calculations and on the drawings. The calculations also show the bearing, eccentricity and sliding checks for each load case. The drawing set has one sheet for each footing arrangement used: toe with no heel, toe with heel, or heel with no toe.
After you accept, the calculations, project summary and drawings are prepared from Project Outputs. See Pay for and download your documents.
Limitations#
Up to five retained heights, each more than 0 mm and no more than 3000 mm.
Backfill soil friction angle, φb and Founding soil friction angle, φf from 26° to 36°.
Backfill soil unit weight, γb and Founding soil unit weight, γf from 14 to 20 kN/m³.
Geotechnical ultimate bearing capacity, qu from 150 to 300 kPa.
Wall cases 3 to 6 only.
The footing is solved as a toe or a heel (a toe can have a heel of the length you set). There is no central footing option.
The wall thickness is 190 mm or 240 mm.
If a shear key is needed and no reinforcement option passes, that height fails. A specific engineering design is needed.
Only heights that pass are included in the drawings.
Common errors and how to fix them#
Geotechnical information required: "Complete the geotechnical report details and soil properties in Project Settings before analysing this retaining wall." Fill in every field in the Geotechnical Properties section of Project Settings, save, and analyse again. See Project Settings missing.
Check geotechnical values: "These inputs differ from the project geotechnical properties. Check they are suitable before continuing." Click Review inputs and correct the values. Or, if the different values are intended, click Continue.
"Project Settings could not be loaded, so the geotechnical information could not be checked. Try again." Check your connection and click Analyse Data again.
"Project Settings earthquake zone is required before running this calculation." or "Project Settings soil class is required before running this calculation." Set Earthquake Zone or Soil Class in Project Settings.
"Project Settings earthquake zone must be zone 1, 2, 3 or 4." or "Project Settings soil class must be A, B, C, D or E." Choose a supported value in Project Settings.
"Must be ≤ 3000 mm" under a height. Each retained height must be no more than 3000 mm.
"Minimum is 26°" under Backfill soil friction angle, φb or Founding soil friction angle, φf, or "Minimum is 150 kPa" / "Maximum is 300 kPa" under Geotechnical ultimate bearing capacity, qu. Enter a value in the range shown under the field.
A height shows Fail. The calculator could not find a wall, footing and shear key that pass for that height. Check the inputs and analyse again. If no combination passes, see When no calculator fits.
"This calculation cannot be accepted or issued. Wall H2 (2000 mm retained height): no shear-key reinforcement option passes. This design is outside the scope of the calculator - a specific engineering design (SED) is required." This can appear on a calculation saved before CALC-012 2.0.0. That height is outside this calculator's scope and needs a specific engineering design. The other heights cannot be accepted while it is in the calculation. See When no calculator fits.
"This calculation cannot be accepted or issued. No standard ArchiSuite detail covers this design: No drawing can be produced for this calculation." No height passed, so there is nothing to draw.
"Permission denied" when you update or delete. Only team admins and editors can change saved calculations. See Teams and permissions.
"This calculation has been accepted and paid for, so it cannot be changed. Use Revise Calculation on Project Outputs to make a revised version." See Revise an accepted calculation.