Calculator guide · CALC-027

Floor Beam Supporting Floor

Size a steel or timber beam that carries internal timber floor joists only, with a floor vibration check and slab-edge or pad checks under each end.

Video: a worked example

One real design taken through this calculator, from Project Settings to the issued documents. Read the worked example and transcript
On this page

Floor Beam Supporting Floor sizes a single-span steel or timber beam that holds up timber floor joists, and nothing else. A typical case is where an internal wall that carries only a timber floor is removed. You choose a passing member, and ArchiSuite then checks the foundation under each end.

Floor Beam Supporting Floor · CALC-027

Size a steel or timber beam supporting internal timber floor joists, with slab-edge checks and pad footings where needed.

Use it when

  • Floor joists are the only load carried by the beam.
  • Single spans up to 10 m inside the building.

Results

  • Steel and timber member options.
  • Support reactions and slab-edge or pad-footing results.
  • Member and support drawing schedules.

Limits

  • No roof, wall or point loads.
  • No decks, balconies, verandahs, cantilevers or continuous spans.
  • Foundation checks assume concrete slab-edge supports.
  • Floor vibration and building bracing are not checked.

Before you start#

This calculator reads one value from your active project's Project Settings: the Geotechnical Ultimate Bearing Capacity, between 150 and 300 kPa. It does not use the wind zone, snow zone, elevation or roof pitch.

Measure these before you start:

  • the beam span

  • the supporting stud height: from the floor or slab to the underside of the beam at a post

  • the joist spans on each side of the beam, or the floor loaded dimension

  • the spacing of the floor joists fixed on top of the beam

Step by step#

  1. Click All Calculators in the sidebar. Under Floor Beams, choose Floor Beam Supporting Floor.

  2. Click New Floor Beam calculation. If you have none yet, click Add Floor Beam Calculation.

  3. In section 1, General Info, enter a Calculation Name, the Beam span and the Supporting stud height. The Span and Supporting stud height sliders on the diagram set the same fields.

  4. In section 2, Floor, choose the Floor type. Then enter either the Floor loaded dimension or the Full floor joist span, and the Joist spacing.

  5. In section 3, Building weights, choose the Roof weight, the Lower-storey wall cladding and the Upper-storey wall cladding. The form needs all three before it will submit.

    Fill in the three sections, then click Analyse Floor Beam
  6. Click Analyse Floor Beam. The Summary table appears.

  7. To see every passing size, click Show All Passing Members (optional).

  8. Click Select on the member you want. ArchiSuite runs the calculation again for that member and checks the foundations. You see "Designation … selected successfully!", and the button changes to Selected.

  9. Click Accept in the Summary header. You see "Calculation accepted successfully!", and the calculation is added to Project Outputs.

    Select a member, then Accept

To change an input later, edit it and click Update Assessment. Then select a member and accept again, because updating clears your selection. Only team admins and editors can update a calculation or select a member.

The inputs#

Click the (i) beside an input, where it appears, to open its ArchiGuide explanation.

General Info. The Beam span is the length of the beam between its supports, up to 10 m. See Beam Span. The Supporting stud height is measured from the floor or slab to the underside of the beam at a post, between 0.3 and 4.0 m. It is printed in the drawing's Support Schedule and does not change the beam design, but you cannot accept the calculation without it. If you leave the Calculation Name blank, the calculation is saved as "Floor Beam Supporting Floor Design".

Floor. The Floor type sets the floor weight and live load used. Choose Timber Floor for an internal timber floor. Enter either the Floor loaded dimension (up to 7 m), or the Full floor joist span. The full floor joist span is both sides of the beam together, and ArchiSuite halves it to get the loaded dimension. Fill in one or the other, not both. The Joist spacing is the spacing of the joists fixed on top of the beam, from 0.1 to 0.6 m. See Top Floor Joist Spacing. The beam's top edge is always taken as held by these joists at that spacing.

Building weights. Choose the Roof weight (Light roof or Heavy roof) and the Lower-storey and Upper-storey wall cladding (Light, Medium or Heavy cladding) of the building. The upper storey cannot have a heavier cladding than the lower storey (NZS 3604:2011 Tables 5.9 and 5.10); the form says so and will not submit. See Roof Type and Wall Cladding Weight. They are used only in the foundation check under each end of the beam: they set how much of the ground's capacity the two-storey building already uses. They add no load to the beam.

  • Floor Beam Span, L (m)Required

    m

  • Floor TypeOptional

    As shown on the form

  • Floor Loaded Dimension / Tributary (m)Optional

    m

  • Full Floor Joist Span (m)Optional

    m

  • Joist Spacing (m)Optional

    m

  • Top Edge Positively RestrainedOptional

    As shown on the form

  • Supporting stud height (m)Optional

    0.3 to 4 m

    If not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.”

  • Roof Weight ClassOptional

    As shown on the form

  • Foundation Cladding CategoryOptional

    As shown on the form

  • Upper-storey wall claddingOptional

    As shown on the form

Read from Floor Beam Supporting Floor (CALC-027, version 4.0.0) as it runs today. The form may also show its own limit beside an input.

Worked example#

Here is a representative example from ArchiSuite's test suite. It is not a design for your project.

WhereInputValue
Project SettingsGeotechnical Ultimate Bearing Capacity300 kPa
General InfoBeam span / Supporting stud height3.0 m / 2.4 m
FloorFloor typeTimber Floor
FloorFloor loaded dimension / Joist spacing2.0 m / 0.6 m

After Analyse Floor Beam, the Summary lists passing steel and timber members, including 150 PFC 17.7 (steel) and 290 x 90 SG8 (timber). With either one selected, the calculation passes, and the slab edge is adequate at both ends, so no pad footing is needed. In the test suite, the timber option is then accepted into Project Outputs.

Results#

  • Summary table. Each row shows the most efficient passing member in one steel type (PFC, UB, UC) or timber group. The columns are Member Type, Most Efficient Passing Member, Max Defl Down (mm), Max Defl Up (mm), Rigidity Ratio, Capacity Ratio and Status, where the Select button is.

  • Floor vibration. Every member offered passes a floor vibration check: its deflection under a 1 kN point load at midspan is no more than 1.0 mm. A member that fails this check is not offered.

  • Show All Passing Members lists every passing size.

  • Foundation. The slab-edge or pad-footing results are in the calculation documents, not in the Summary table.

  • Support Schedule. ArchiSuite designs the supporting studs for the beam's reactions and the supporting stud height, and checks them for buckling at that height. On the drawing, the Support Schedule shows one support for both ends: two to four SG8 studs, in 90×45, 140×45 or either size (for example 2 / 90×45 or 2 / 140×45 studs). A steel beam stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate or the downward reaction at a support is over 50 kN. The supporting stud height is printed beside the support. A calculation accepted before the studs were designed this way keeps the support it was accepted with.

  • If no member passes, you see "No member passes - change the inputs."

Limitations#

  • The beam carries floor load only. There are no inputs for a roof, wall or point load.

  • The calculation states its own scope: "Isolated single-span simply supported floor beams only — not continuous bearers, two-span NZS 3604 bearers, cantilevers, deck/balcony/veranda beams or wet-in-service framing."

  • The beam span can be up to 10 m and the floor loaded dimension up to 7 m. The form accepts a full floor joist span of up to 12 m.

  • The foundation check assumes each end sits on a concrete slab edge.

  • You cannot choose the member type, minimum bearing length (90 mm) or pad width (300 mm).

  • The supporting stud height must be between 0.3 and 4.0 m. ArchiSuite checks the supporting studs, and the SHS post where one is used, for buckling at that height. The studs are checked with rows of dwangs at 1350 mm centres or closer, as the drawing notes.

  • The supports are SG8 studs, 90×45 or 140×45, two to four to a support, or the 75×5 SHS post under a steel beam. You cannot choose the stud grade, size or number.

Common errors and how to fix them#

  • "Project Settings geotechnical ultimate bearing capacity is required before running this calculation." Enter it (150 to 300 kPa) in Project Settings and click Update Project. See Project settings missing.

  • "Please enter either Floor Loaded Dimension / Tributary OR Full Floor Joist Span." Fill in one of the two floor fields.

  • "Floor loaded dimension must be greater than 0." Enter a loaded dimension or full floor joist span above 0.

  • "This project already has a calculation named '…'. Give this one a different name, so its drawings and calculations can be told apart." Give the calculation its own name. This also happens if you leave the name blank on a second floor beam, because both get the default name.

  • "No member passes - change the inputs." See No member passes.

  • "Failed to select floor beam supporting floor beam" The member could not be selected, for example because it is no longer a passing option. Click Update Assessment and choose a member from the new list.

  • "Project Settings changed - press Update Assessment. Changed since this calculation was assessed: Ground Bearing Capacity (GUBC)." Click Update Assessment, then select a member and accept again.

  • "Select a passing beam and complete the foundation check before accepting this calculation" Select a member first.

  • "Supporting stud height in section 1 (General Info) is not the saved value (…). …" Click Update Assessment to save the height, select the member again, then accept.

  • "This calculation cannot be accepted or issued. Floor beam … fails the floor vibration check: …" This can happen with a result stored before the check existed. Open the calculation, click Update Assessment and select another floor beam. If the calculation is paid, use Revise Calculation.

  • "This calculation cannot be accepted or issued. The supporting stud height is missing. …" Enter the Supporting stud height, click Update Assessment, select the member again and accept.

  • "… the slab edge cannot carry the load and no pad footing could be designed for it. A specific engineering design is required." See When no calculator fits.

Worked example

Was this helpful?

How-toProject SettingsEvery field on the Project Settings page - what it means, the accepted options and limits, which calculators use it, and what happens to existing calculations when you change it.Read Calculator guideLintel Supporting Roof, Wall & Floor JoistsSize a steel or timber lintel that carries roof framing, the wall standing on it and timber floor joists, with a floor vibration check and slab-edge or pad checks.Read How-toCheck and Accept ResultsHow to read a calculator's results, choose a passing member, and press Accept so the calculation moves into Project Outputs.Read TroubleshootingNo Member PassesWhat the "No member passes - change the inputs." notice means on the lintel and beam calculators, and which inputs to check first.Read TroubleshootingWhy an Input Is RefusedWhat the red messages under an input and the error toasts after Analyse mean, grouped by cause, with the fix for each.Read TroubleshootingProject Settings Missing or Out of RangeFix messages such as "Roof Pitch is missing or out of range…" or "Project Settings … is required before running this calculation" by completing Project Settings.Read TroubleshootingCannot Accept, Pay or DownloadThe real messages you see when Accept, payment or a document download is refused, what each one means, and how to fix it.Read How-toRevise an Accepted CalculationA paid calculation is locked. Change it through a draft revision, then Update & Accept and pay. Your issued documents stay in place until the revision replaces them.Read