Worked example · CALC-034

How to Use the Roof Beam Calculator: Worked Example

A step-by-step worked example of the Roof Beam Supporting Roof Framing/Trusses calculator, with a screen-recorded video - a 4.2 m timber roof beam under a light roof, including wind uplift, from Project Settings to the accepted calculation.

Author
ArchiSuite
Technical review:
Michael Sheridan
Reviewed:
Published:
On this page

This worked example takes one real design through the Roof Beam Supporting Roof Framing/Trusses calculator, from Project Settings to an accepted calculation in Project Outputs. The calculator sizes a single-span steel or timber roof beam, such as a beam on two posts carrying the rafters, that carries roof framing only. It takes the wind and snow from your Project Settings, so it also shows what wind uplift does to a light roof. Every value below was entered in ArchiSuite, and every result was read from it.

Video tutorial#

The whole example, including a quick look at its documents, in about three minutes. Each step is captioned on screen; closed captions (CC) and the transcript at the end of this page give the same steps as text.2:50Read the transcript

The example project#

A single-storey house is getting a cathedral ceiling over its living room, with an exposed roof beam along the middle of the roof, carried on a post at each end. The roof beam spans 4.2 m between the posts and carries the rafters only: no wall, floor or point load comes onto it. The rafters span onto the beam from the walls on each side, which are 6.0 m apart, at 900 mm centres, under a light (metal) roof.

What the example assumes:

  • The beam carries roof load only: the roofing and rafters, snow and wind. There is no wall, floor or point load on it.

  • It is a single span, simply supported on a post at each end.

  • Each end of the beam sits on the edge of the concrete ground-floor slab, which is what the foundation check assumes.

  • The values are an illustration. They are not defaults for your project.

Step 1: Open the calculator#

  1. Make the project active. Its name is shown under Active project at the top of every page.

  2. Click All Calculators in the sidebar.

  3. Under Roof Beams, choose Roof Beam Supporting Roof Framing/Trusses.

  4. Click Add Roof Beam Calculation, or New Roof Beam Calculation once the project has one.

All Calculators: Roof Beams → Roof Beam Supporting Roof Framing/Trusses

Step 2: Check the project information#

Unlike the floor beam, this calculator reads all five site settings from the active project's Project Settings:

Project SettingValue usedUnitWhy it matters here
Wind ZoneHighSets the wind pressure on the roof: the downward wind load and the uplift the beam and its supports must resist.
Snow ZoneN1With the elevation and the roof pitch, sets the snow load on the roof.
Elevation80mThe site's height above sea level, used for the snow load (blank in Snow Zone N0).
Roof Pitch20degThe roof slope, used for the snow load; with more than one pitch, use the lowest.
Geotechnical Ultimate Bearing Capacity300kPaUsed in the foundation check under each end of the beam. 300 kPa is the ultimate bearing pressure that good ground must withstand under NZS 3604; use your own site's value.

These come from Project Settings and are not entered on the form. If one is missing, the calculation is refused when you click Analyse Roof Beam. The values here are an example; use your own site's zones, elevation and pitch.

Project Settings: the wind zone, snow zone, elevation, roof pitch and bearing capacity all feed the roof beam

Step 3: Enter the beam design inputs#

The form has three sections. The arrangement diagram above it redraws the span and the supporting stud height as you type, and the letters beside some labels (A, B, C) point to the 3D model.

The new calculation, before any inputs

These are the exact values entered in the recording:

SectionFieldValue usedUnitWhat it means
General InfoCalculation NameRB1 - Living room roof beam-Names the calculation in Project Outputs and on the drawings and calculations. Each calculation in a project needs its own name.
General InfoBuilding storeysSingle storey-Single storey unless the roof beam is in the upper storey of a two-storey building. This example's beam is in a single-storey house.
General InfoBeam span4.2mThe length of the beam between its posts. The form accepts up to 10 m.
RoofRoof typeLight-Light or Heavy roofing. Light suits a metal roof.
RoofRoof loaded dimension(left blank)mLeft blank. It is the alternative to the roof span: the width of roof the beam carries. It greys out once a roof span is entered.
RoofRoof span6.0mThe full roof span, wall centreline to wall centreline. ArchiSuite takes half of it, 3.0 m, as the loaded dimension of a beam along the middle of the roof. The form accepts up to 12 m.
RoofRafter / truss spacing0.9mThe spacing of the rafters bearing on the beam. They hold its top edge sideways. Up to 1.2 m; left blank, 1.2 m is used and saved.
WallSupporting stud height2.4mFrom the floor or slab to the underside of the beam at a post. ArchiSuite designs the supporting studs for this height and prints it in the drawing's Support Schedule; it does not change the beam design. The form accepts 0.3 to 4.0 m.
WallWall cladding typeLight-The building's wall cladding: Light, Medium or Heavy. Used only in the foundation check under each end; it adds no wall weight to the beam.
The completed inputs for RB1 - Living room roof beam

Step 4: Run the calculation#

Click Analyse Roof Beam. The button shows Processing… while the calculation runs (it works through the wind and snow load cases, which can take a little while), and the Summary table then appears below the form. If an input is missing or out of range, the form says so beside the field and does not submit; a missing Project Setting is refused with a message naming it.

Step 5: Understand the results#

The Summary#

The Summary lists the most efficient passing member of each member type: three steel sections and twelve timber groups, including sawn SG8. These are the values ArchiSuite showed for this example. The member selected below is in bold.

Member TypeMaterialMost Efficient Passing MemberMax Defl Down (mm)Max Defl Up (mm)Rigidity RatioCapacity Ratio
PFCSteel150 PFC 17.74.21-4.383.1991.591
UBSteel180 UB 16.13.29-3.474.0301.086
UCSteel100 UC 14.810.84-11.621.2041.117
SG8Timber290 x 90 SG811.08-7.611.2631.318
HY90Timber240 x 90 hy9011.21-7.591.2492.307
HYSPANTimber240 x 63 hySPAN11.19-7.961.2511.575
HYONETimber240 x 90 hyONE6.65-4.502.1044.411
LVL11Timber610 x 45 LVL111.21-0.7811.6181.011
LVL13Timber240 x 63 LVL1311.16-7.981.2541.492
GL8Timber360 x 65 GL85.44-3.712.5741.020
GL10Timber315 x 65 GL106.42-4.462.1811.037
GL12Timber270 x 65 GL128.76-6.221.5981.002
PROLAM PL8Timber240 x 88 Prolam PL813.44-9.301.0421.268
PROLAM PL12Timber315 x 63 Prolam PL125.74-4.012.4371.079
PROLAM PL17Timber190 x 88 Prolam PL1712.74-9.091.0991.864
The Summary after Analyse Roof Beam

What the columns mean:

  • Max Defl Down (mm) is the member's largest downward deflection. Max Defl Up (mm) is its largest upward deflection, shown as a negative number: wind uplift on a light roof lifts the beam.

  • Rigidity Ratio is the smallest of the member's deflection checks, each one deflection limit ÷ calculated deflection. (A roof beam has no floor vibration check.)

  • Capacity Ratio is the smallest of its strength checks, each one capacity ÷ demand: bending downwards, bending upwards under uplift, and shear.

  • A ratio of 1.0 or more passes. Every row in the Summary passes all of these checks.

  • Show All Passing Members lists every passing size, not only the most efficient of each type.

Selecting a member#

The example selects 290 x 90 SG8. It is the sawn-timber (SG8) row: a common size for an exposed roof beam. Choose the member that suits your project: every row in the Summary passes the calculator’s checks.

Click Select on its row. ArchiSuite runs the calculation again for that member and checks the foundation under each end, then shows:

After Select, the row shows SELECTED

The selected member's results#

These are the results ArchiSuite stored for 290 x 90 SG8:

ResultValue
Selected member290 x 90 SG8
ResultPass
Roof dead load G0.30 kPa
Roof live load Q0.25 kPa
Roof loaded dimension3.00 m
Roof dead line load on the beam0.90 kN/m
Roof live line load on the beam0.75 kN/m
Maximum bending moment M*7.32 kNm
Maximum shear V*6.97 kN
Reaction at each end (ULS, down)4.93 kN
Uplift at each end6.97 kN
Maximum deflection (service)11.08 mm
Existing slab edge adequateYes
Slab-edge bearing length required144 mm

Strength and serviceability checks#

The Structural Calculations document for this example lists its governing checks. Utilisation is demand ÷ capacity or limit, the inverse of the ratios in the Summary: the governing deflection utilisation of 0.79 (11.08 mm against 14.00 mm) is the Rigidity Ratio of 1.263, and the upward-bending utilisation of 0.76 (7.32 kNm against 9.65 kNm) is the Capacity Ratio of 1.318. For this light roof in a High wind zone, uplift governs the strength of the beam, not the downward load.

PartCheckDemandCapacity or limitUtilisation
Roof beamBending, sagging (1.2G + 1.5Qr (UDL))5.18 kNm11.30 kNm0.46
Roof beamBending, hogging (0.9G - Wu)7.32 kNm9.65 kNm0.76
Roof beamShear (ULS)6.97 kN42.32 kN0.16
Roof beamDeflection, S3a: G + Ws (down) (L/300) – governs11.08 mm14.00 mm0.79
Supporting studs2 / 90×45 studs: compression (bending and compression (eq 3.23), 1.2G + 1.5Qr (UDL))4.93 kN20.29 kN0.24
Supporting studs2 / 90×45 studs: tension, 1 full-height stud (0.9G - Wu) – governs6.97 kN13.27 kN0.53
Supporting studs2 / 140×45 studs: compression (bending and compression (eq 3.24), 1.2G + 1.5Qr (UDL))4.93 kN47.01 kN0.10
Supporting studs2 / 140×45 studs: tension, 1 full-height stud (0.9G - Wu)6.97 kN21.91 kN0.32
Slab edge (option 1)Bending (bearing or uplift length)2.39 kNm23.23 kNm0.10
Slab edge (option 1)Shear (bearing or uplift length)5.23 kN30.77 kN0.17
Slab edge (option 1)Bearing length towards the other support (L/2)72 mm4128 mm0.02
Slab edge (option 1)Uplift length towards the other support (L/2) – governs914 mm3286 mm0.28
Pad footing (option 2)Uplift (0.9G + wind or earthquake) – governs6.97 kN7.14 kN0.98
Pad footing (option 2)Bearing pressure (G; ψcQ; Ws)11.1 kPa100.0 kPa0.11
Pad footing (option 2)Punching shear (1.2G;ψcQ; Wd)0.070 MPa1.571 MPa0.04
Pad footing (option 2)Beam shear (1.2G;ψcQ; Wd)0.042 MPa0.800 MPa0.05
Pad footing (option 2)Bending (1.2G;ψcQ; Wd)1.96 kNm44.35 kNm0.04

The document's conclusion:

Uplift and the foundations#

Each end of the beam is pushed down by 4.93 kN and lifted by 6.97 kN (ULS): the uplift is the larger. The foundation options are alternatives at each end: the existing slab edge (here with 2-HD12 enhancement steel, a 144 mm bearing length and an 1829 mm uplift length) or a 1050 × 1050 × 300 mm pad footing, whose size is set by the uplift it must hold down. Build either adequate option.

Warnings and limitations#

  • "Uplift connections: the connection of the beam to its supports is selected from the standard details and checked for the beam's uplift reaction in the support design." The fixing of the rafters or trusses to the beam is outside this calculation.

  • The calculation states its own scope: "Not applicable to rafters, veranda beams, purlins, battens or hip-supported ridge beams."

  • ArchiSuite designs the supporting studs under the beam for its reactions and the supporting stud height, and checks them for buckling at that height. The Support Schedule on the drawings shows one support for both ends: two to four SG8 studs in 90×45, 140×45 or either size (here 2 / 90×45 or 2 / 140×45 studs). A steel beam stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate or the downward reaction at a support is over 50 kN.

  • The Wall cladding type adds no load to the beam. It is used only in the foundation check.

Step 6: Access the documentation#

  1. Click Accept in the Summary header. ArchiSuite shows:

  1. Open Project Outputs from the sidebar. The calculation is listed under Accepted calculator outputs included with its status.

Project Outputs lists the accepted calculation (prices blurred)

What you can see and download, and when:

  • On screen. The Summary, the selected member and its pass status are in the calculator itself, as soon as you analyse and select.

  • The document packs. Project Outputs offers three PDFs: the Project Summary, the Structural Calculations (every calculation page, including the governing checks, the uplift and the foundation details above) and the Structural Drawings. They download once every accepted output is paid.

  • Documents that wait for review. Where an Engineering Review is included (it always is for an account without a Licensed Building Practitioner number), the downloads also wait until ArchiSuite has reviewed the documents and released them for issue. See Pay and download your documents.

The document packs open after payment and, where included, Engineering Review

Once the review is released, the panel says so and every download opens.

After payment and Engineering Review: the documents are released for issue

The video ends with a quick look through the documents this example produced, as issued: the Project Summary; the PS1 Producer Statement - Design and its Schedule, shown unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; every page of the Structural Calculations; and every sheet of the Structural Drawings.

Common mistakes#

  • A missing Project Setting. "Project Settings wind zone is required before running this calculation." (or snow zone, elevation, roof pitch, or geotechnical ultimate bearing capacity). Complete it in Project Settings and click Update Project. See Project settings missing.

  • Both roof fields, or neither. Enter the Roof loaded dimension or the Roof span. The calculator refuses "Enter either the roof loaded dimension, or the full roof span - not both." and, with neither, "Enter the roof loaded dimension, or the full roof span."

  • The wrong span. The roof span is wall centreline to wall centreline, and ArchiSuite halves it. If the beam is not along the middle of the roof, it does not carry half the span: enter the loaded dimension instead.

  • A wide rafter spacing. The spacing can be up to 1.2 m; a wider one is refused, not rounded down. A wider spacing needs a specific engineering design. See When no calculator fits.

  • The wrong beam. It is for a beam carrying roof framing only. It is not for rafters, veranda beams, purlins, battens or hip-supported ridge beams, or a beam with a point load, wall or floor on it.

  • Editing after selecting. Changing an input and clicking Update Assessment clears your selection: select the member and accept again.

  • The same name twice. Each calculation in a project needs its own name. Change the Calculation Name.

  • Nothing passes. "No member passes - change the inputs." See No member passes.

Engineering note#

Recorded with CALC-034 Roof Beam Supporting Roof Framing/Trusses version 0.33.0 on 2026-11-25.

Video transcript#

  • 0:07 The project Worked Example - Roof Beam is active. This calculator reads five Project Settings: Wind Zone High, Snow Zone N1, Elevation 80 m, Roof Pitch 20 degrees and a Geotechnical Ultimate Bearing Capacity of 300 kPa.

  • 0:18 Under All Calculators, in Roof Beams, open Roof Beam Supporting Roof Framing/Trusses, then Add Roof Beam Calculation. The calculator sizes a single-span steel or timber beam, such as a beam on two posts carrying the rafters, that carries roof framing only.

  • 0:28 The form has three sections: General Info, Roof and Wall. The arrangement diagram above it follows the values as you type.

  • 0:32 In General Info, the calculation is named RB1 - Living room roof beam. The Beam span is 4.2 m, post to post. The Supporting stud height is 2.4 m, from the floor to the underside of the beam at a post.

  • 0:45 In Roof, Light is already selected for the metal roof. Instead of a loaded dimension, the Roof span is entered: 6.0 m, wall to wall; ArchiSuite takes half of it, 3.0 m, and the Roof loaded dimension field greys out. The Rafter / truss spacing is 0.9 m.

  • 0:57 In Wall, Light is already selected for the wall cladding weight. It is used only in the foundation check under each end and adds no wall weight to the beam.

  • 1:02 Analyse Roof Beam runs the calculation with the wind and snow from Project Settings. When it finishes, the Summary lists the most efficient passing member of each member type.

  • 1:10 Every row passes. Max Defl Down is the largest downward deflection; Max Defl Up is negative because wind uplift lifts the beam. The Rigidity Ratio is the smallest of the deflection checks, limit divided by deflection; the Capacity Ratio is the smallest strength check, capacity divided by demand, for bending either way and shear. Both must be at least 1.0. The SG8 row, 290 x 90 SG8, deflects 11.08 mm down and has a Rigidity Ratio of 1.263 and a Capacity Ratio of 1.318. Show All Passing Members lists every size that passes.

  • 1:31 Select on the 290 x 90 SG8 row selects that member. ArchiSuite runs the calculation again for it, checks the foundations and shows a confirmation. Accept then adds the calculation to Project Outputs.

  • 1:41 Project Outputs lists RB1 - Living room roof beam as an accepted output. The Structural Calculations and Structural Drawings, with the full checks, the uplift and the foundation details, download from here once the outputs are paid and, where Engineering Review is included, reviewed and released. Prices are hidden in this video.

  • 1:54 After payment and Engineering Review (not shown), Project Outputs shows the document packs ready to download. A quick look through what they contain: the Project Summary, with the project and every accepted calculation; the PS1 Producer Statement - Design and its Schedule, shown here unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; the Structural Calculations; and the Structural Drawings.