Calculator guide · CALC-034

Roof Beam Supporting Roof Framing/Trusses

Size a steel or timber roof beam, such as a ridge beam on two posts, that carries roof framing only, with wind and snow from Project Settings and slab-edge or pad checks.

Video: a worked example

One real design taken through this calculator, from Project Settings to the issued documents. Read the worked example and transcript
On this page

Roof Beam Supporting Roof Framing/Trusses sizes a single-span steel or timber roof beam that carries roof framing only. An example is a ridge beam on two posts that the rafters or trusses bear on. The roof load includes wind (down and uplift) and snow from your Project Settings. You choose a passing member, and ArchiSuite then checks the foundation under each end.

Before you start#

This calculator takes five values from your active project's Project Settings. You do not enter them on the form:

  • Wind Zone and Snow Zone

  • Elevation (0 to 800 m; left blank for Snow Zone N0)

  • Roof Pitch (0 to 45 degrees; if the roof has more than one pitch, use the lowest; not needed in Snow Zone N0)

  • Geotechnical Ultimate Bearing Capacity (150 to 300 kPa)

If you tick Beams & lintels under What are you designing? in Project Settings, the page shows these five fields. Save them with Update Project. If one of them is missing, the form does not warn you. The calculation is refused when you click Analyse Roof Beam.

Measure these before you start:

  • the beam span, post to post

  • the supporting stud height: from the floor or slab to the underside of the beam at a post

  • the roof loaded dimension, or the full roof span from wall centreline to wall centreline

  • the rafter or truss spacing

Step by step#

  1. Click All Calculators in the sidebar. Under Roof Beams, choose Roof Beam Supporting Roof Framing/Trusses.

  2. Click New Roof Beam Calculation. If you have none yet, click Add Roof Beam Calculation.

  3. In section 1, General Info, enter the Calculation Name, choose the Building storeys (Single storey unless the beam is in the upper storey of a two-storey building), and enter the Beam span.

  4. In section 2, Roof, choose the Roof type. Then enter either the Roof loaded dimension or the Roof span, and the Rafter / truss spacing.

  5. In section 3, Wall, enter the Supporting stud height and choose the Wall cladding type. For Two storey, enter the upper-storey and the lower-storey supporting stud heights and wall cladding types. The Span and Supporting stud height sliders on the diagram set the same fields.

    Fill in the three sections, then click Analyse Roof Beam
  6. Click Analyse Roof Beam. The Summary table appears.

  7. To see every passing size, click Show All Passing Members (optional).

  8. Click Select on the member you want. ArchiSuite runs the calculation again for that member and checks the foundations. You see "Designation … selected successfully!", and the button changes to Selected.

  9. Click Accept in the Summary header. You see "Calculation accepted successfully!", and the calculation is added to Project Outputs.

    Select a member, then Accept

To change an input later, edit it and click Update Assessment. Then select a member and accept again, because updating clears your selection. Only team admins and editors can update a calculation or select a member.

The inputs#

Click the (i) beside an input, where it appears, to open its ArchiGuide explanation.

General Info. The Beam span is the length of the beam between its posts, up to 10 m. See Beam Span. It is B on the 3D model.

Roof. For Roof type, choose Light or Heavy roofing. See Roof Type. Enter either the Roof loaded dimension (up to 7 m), or the Roof span (A on the model, up to 12 m). If you enter the roof span, the loaded dimension is half of it. There is no eave / overhang input: an overhang loads the walls, not this beam. The Rafter / truss spacing is the spacing of the rafters or trusses bearing on the beam. They hold the beam's top edge sideways. It can be up to 1.2 m. Leave it blank to use 1.2 m, and that value is saved with the calculation.

Wall. The Supporting stud height is measured from the floor or slab to the underside of the beam at a post, between 0.3 and 4.0 m (C on the model). It is printed in the drawing's Support Schedule and does not change the beam design, but you cannot accept the calculation without it. The Wall cladding type of the building is used in the foundation check under each end: it sets how much of the ground's capacity counts as already used by the house's walls. It adds no wall weight to the beam.

Two storey. Building storeys is Single storey unless you change it. Choose Two storey where the roof beam is in the upper storey of a two-storey building, so its supports stand on the mid-floor above lower-storey supports. The form then asks for four wall inputs. The Upper-storey supporting stud height and the Upper-storey wall cladding type are the two single-storey inputs, now describing the upper storey. The Lower-storey supporting stud height (0.3 to 3.0 m) and the Lower-storey wall cladding type describe the storey below. The upper-storey cladding cannot be heavier than the lower-storey cladding. Switching back to Single storey hides the lower-storey inputs, and a single-storey calculation does not use them.

In Two storey mode ArchiSuite designs the upper-storey supports, the mid-floor connection and the lower-storey supports from the selected member's reactions. Uplift is checked at the top connection, the upper-storey supports and the mid-floor connection. The lower-storey supports are designed for compression, and the foundation for bearing under the roof beam's downward reaction.

  • Beam Span, L (m)Required

    m

  • Roof TypeRequired

    As shown on the form

  • Wall cladding typeOptional

    light · medium · heavy

  • Roof Loaded Dimension (m)Optional

    m

  • Full Roof Span (m)Optional

    m

  • Rafter / Truss Spacing (m)Optional

    m

  • Supporting stud height, C (m)Optional

    0.3 to 4 m

    If not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.”

  • Building storeysOptional

    single · double

  • Lower-storey wall cladding typeOptional

    light · medium · heavy

  • Lower-storey supporting stud height (m)Optional

    m

Read from Roof Beam Supporting Roof Framing/Trusses (CALC-034, version 0.33.0) as it runs today. The form may also show its own limit beside an input.

Worked example#

Here is a representative example from ArchiSuite's test suite. It is not a design for your project.

WhereInputValue
Project SettingsWind Zone / Snow ZoneHigh / N1
Project SettingsElevation / Roof Pitch100 m / 15°
Project SettingsGeotechnical Ultimate Bearing Capacity300 kPa
General InfoBeam span / Supporting stud height3.6 m / 2.4 m
RoofRoof type / Roof loaded dimensionLight / 2.4 m
RoofRafter / truss spacing0.9 m
WallWall cladding typeLight

After Analyse Roof Beam, the Summary lists passing steel and timber members, including 150 PFC 17.7 (steel) and 240 x 90 SG8 (timber). With either one selected, the calculation passes, and the slab edge is adequate at both ends, so no pad footing is needed. With the timber option selected, the High wind zone gives an uplift at both supports, and the drawing shows it. On the drawing's Support Schedule, both the steel and the timber beam stand on timber (SG8) stud supports.

Results#

  • Summary table. Each row shows the most efficient passing member in one steel type (PFC, UB, UC) or timber group. The columns are Member Type, Most Efficient Passing Member, Max Defl Down (mm), Max Defl Up (mm), Rigidity Ratio, Capacity Ratio and Status, where the Select button is.

  • Show All Passing Members lists every passing size.

  • Foundation. The slab-edge or pad-footing results are in the calculation documents, not in the Summary table.

  • Support Schedule. ArchiSuite designs the supporting studs for the beam's reactions and the supporting stud height. On the drawing, the Support Schedule shows one support for both ends: two to four SG8 studs, in 90×45, 140×45 or either size (for example 2 / 90×45 or 2 / 140×45 studs). A steel beam stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate, where the downward reaction at a support is over 50 kN, or where the uplift is over 24 kN. The supporting stud height is printed beside the support. A calculation accepted before the studs were designed this way keeps the support it was accepted with.

  • Two storey. The upper-storey supports, the mid-floor connection and the lower-storey supports are not shown in the Summary table. They are in the calculation documents, the drawing and the Project Summary.

  • If no member passes, you see "No member passes - change the inputs."

Limitations#

  • The beam carries roof load only. There are no inputs for point loads (another roof beam, a girder or a post), a wall or floor above, or a cantilever.

  • The beam is a single span, up to 10 m. The roof loaded dimension can be up to 7 m, the roof span up to 12 m and the rafter / truss spacing up to 1.2 m. A larger rafter spacing is refused, not rounded down.

  • The foundation check assumes each end sits on a concrete slab edge.

  • You cannot choose the member type, minimum bearing length (90 mm) or pad width (300 mm).

  • Two storey: the lower-storey supports are two to four full-height timber studs, carrying up to 50 kN, and are never shallower than the upper-storey studs. The lower-storey supporting stud height must be between 0.3 and 3.0 m. Where no standard support or mid-floor connection covers the design, it needs a specific engineering design and cannot be accepted.

  • Uplift connections: ArchiSuite selects the connection of the beam to its supports from the standard details and checks it for the beam's uplift. In Two storey mode it does the same for the mid-floor connection. It does not design the fixing of the rafters or trusses to the beam.

  • The supporting stud height must be between 0.3 and 4.0 m. ArchiSuite checks the supporting studs, and the SHS post where one is used, for buckling at that height. The studs are checked with rows of dwangs at 1350 mm centres or closer, as the drawing notes.

  • The supports are SG8 studs, 90×45 or 140×45, two to four to a support, or the 75×5 SHS post under a steel beam. You cannot choose the stud grade, size or number.

  • You cannot accept a design that the standard drawings do not cover. Examples: a timber beam with more than 24 kN uplift or more than 50 kN downward reaction at a support, or any beam with more than 30 kN uplift.

Common errors and how to fix them#

  • "Project Settings wind zone is required before running this calculation." (or snow zone, elevation, roof pitch, or geotechnical ultimate bearing capacity) Complete that field in Project Settings, click Update Project, then analyse again. See Project settings missing.

  • "Beam span must be greater than 0 m and at most 10 m. You entered … m." Enter a span up to 10 m. The form shows "Must be greater than 0 and at most 10 m" before you submit.

  • "Enter the roof loaded dimension, or the full roof span." Fill in one of the two roof fields.

  • "Enter either the roof loaded dimension, or the full roof span - not both." Clear one of them.

  • "rafter restraint spacing … m exceeds 1.2 m. …" Enter the actual rafter or truss spacing, up to 1.2 m. A wider spacing needs a specific engineering design. See When no calculator fits.

  • "Wall cladding type is required (Light, Medium or Heavy)." Choose the Wall cladding type.

  • "The roof beam calculation stopped: …" The calculation could not finish for the reason given. Check the Project Settings and inputs it names.

  • "This project already has a calculation named '…'. …" Change the Calculation Name.

  • "No member passes - change the inputs." See No member passes.

  • "Project Settings changed - press Update Assessment. Changed since this calculation was assessed: …" Click Update Assessment, then select a member and accept again.

  • "This roof beam was calculated with the superseded floor-beam method (no wind or snow). …" This is an older calculation. Open it, enter the Wall cladding type and the Rafter / truss spacing, and click Update Assessment. Then select a roof beam. If it is paid, use Revise Calculation.

  • "Select a passing beam and complete the foundation check before accepting this calculation" Select a member first.

  • "Supporting stud height, C in section 3 (Wall) is not the saved value (…). …" Click Update Assessment to save the height, select the member again, then accept.

  • "Lower-storey wall cladding type is required for a two-storey design." Choose the Lower-storey wall cladding type, or set Building storeys back to Single storey.

  • "Lower-storey supporting stud height (m) must be between 0.3 and 3.0 m." Enter a lower-storey supporting stud height within that range. The form shows "Allowed range: 0.3 – 3.0 m".

  • "Upper cladding mass cannot exceed lower cladding mass as per NZS 3604:2011 Tables 5.9 and 5.10." Choose a lower-storey wall cladding type at least as heavy as the upper-storey one.

  • "Building storeys in section 1 (General Info) is not the saved value (…). Save it with the "Update Assessment" button, which analyses the calculation again, select the member again, then accept." The storey mode on screen has not been saved. The same message names the Lower-storey supporting stud height or the Lower-storey wall cladding type when that is the unsaved input. Click Update Assessment, select the member again, then accept.

  • "This calculation cannot be accepted or issued. The supporting stud height is missing. …" Enter the Supporting stud height, click Update Assessment, select the member again and accept.

  • "… the slab edge cannot carry the load and no pad footing could be designed for it. A specific engineering design is required." See When no calculator fits.

Worked example