Calculator guide · CALC-002
Lintel Supporting Roof, Wall & Floor Joists
Size a steel or timber lintel that carries roof framing, the wall standing on it and timber floor joists, with a floor vibration check and slab-edge or pad checks.
On this page
Lintel Supporting Roof, Wall & Floor Joists sizes a single-span steel or timber lintel over an opening that has more above it, such as a ground-floor opening under an upper floor and wall. The lintel carries three loads, all spread along its length: roof framing, the wall standing on it and timber floor joists bearing on it. You choose a passing member, and ArchiSuite then checks the foundation under each end.
Lintel Supporting Roof, Wall and Floor Joists · CALC-002
Size a steel or timber lintel carrying roof framing, an upper wall and timber floor joists.
Use it when
- An opening carries roof, wall and timber floor loads.
- Single spans up to 10 m with evenly distributed loading.
Results
- Steel and timber member options.
- Support reactions and slab-edge or pad-footing results.
- Member and support drawing schedules.
Limits
- No point loads, decks, verandahs, cantilevers or continuous spans.
- Compression-edge restraint at 600 mm centres or closer is assumed.
- Foundation checks assume concrete slab-edge supports.
- Timber is for internal, dry use.
Before you start#
This calculator takes five values from your active project's Project Settings. You do not enter them on the form:
Wind Zone and Snow Zone
Elevation (0 to 800 m; left blank for Snow Zone N0)
Roof Pitch (0 to 45 degrees; if the roof has more than one pitch, use the lowest; not needed in Snow Zone N0)
Geotechnical Ultimate Bearing Capacity (150 to 300 kPa)
If you tick Beams & lintels under What are you designing? in Project Settings, the page shows these five fields. Save them with Update Project.
Measure these before you start:
the beam span
the supporting stud height under the lintel, plate to plate
the roof loaded dimension, or the eave / overhang and the roof span
the height of the wall standing on the lintel
the floor loaded dimension, or the floor joist span
Step by step#
Click All Calculators in the sidebar. Under Lintels, choose Lintel Supporting Roof, Wall & Floor Joists.
Click New Lintel opening. If you have no calculations of this type yet, the button reads Add Lintel Calculation.
In section 1, General Info, enter the Calculation Name, the Beam span and the Supporting stud height.
In section 2, Roof, choose the Roof type. Then enter either the Roof loaded dimension, or both the Eave / overhang and the Roof span.
In section 3, Wall, choose the Lower-storey wall cladding and the Upper-storey wall cladding, and enter the Wall height above lintel.
In section 4, Floor, enter either the Floor loaded dimension or the Floor joist span.
Four sections: General Info, Roof, Wall, Floor Click Analyse Beam opening. The Summary table appears.
To see every passing size, click Show All Passing Members (optional).
Click Select on the member you want. ArchiSuite runs the calculation again for that member and checks the foundations. The button changes to Selected, and you see "Beam selected successfully!".
Click Accept in the Summary header. You see "Calculation accepted successfully!", and the calculation is added to Project Outputs.
Select a member, then Accept
To change an input later, edit it and click Update Assessment. Then select a member and accept again, because updating clears your selection. Only team admins and editors can update a calculation or select a member.
The inputs#
Click the (i) beside an input, where it appears, to open its ArchiGuide explanation.
General Info. The Beam span is the length of the lintel between its supports. See Beam Span. The Supporting stud height is the height of the studs under the lintel, measured plate to plate: from the top of the bottom plate to the underside of the top plate (C on the 3D model). It must be between 0.3 and 4.0 m. It is printed in the drawing's Support Schedule and does not change the lintel design. You cannot accept the calculation without it.
Roof. For Roof type, choose Light or Heavy roofing. See Roof Type. Enter the Roof loaded dimension, or the Eave / overhang and the Roof span. ArchiSuite then works the loaded dimension out as the eave / overhang plus half the roof span.
Wall. The Wall height above lintel is the height of the wall standing on the lintel, from floor to top plate, between 0.3 and 4.8 m. See Wall Height. It is not the supporting stud height below the lintel. The Upper-storey wall cladding is that wall's Wall cladding weight: it adds the weight of that wall to the lintel. The Lower-storey wall cladding is the cladding of the storey below; it is used only in the foundation check under each end of the lintel, where the two claddings and the roof set how much of the ground's capacity the building already uses. The upper storey cannot have a heavier cladding than the lower storey (NZS 3604:2011 Tables 5.9 and 5.10); the form says so and will not submit.
Floor. The floor is always treated as a timber floor. The Floor loaded dimension is the width of floor bearing on the lintel: half of each joist span bearing on it, added together. If the joists bear from one side only, you can enter that full Floor joist span instead, and ArchiSuite halves it. If they bear from both sides, enter the loaded dimension.
| Input | Accepted values | Required |
|---|---|---|
| Roof Type | light · heavy | Yes |
| Wall Cladding Weight | light · medium · heavy | Yes |
| Lower-storey wall cladding | light · medium · heavy | No |
| Beam Span, L (m) | more than 0 and up to 10 mIf not: “Beam Span, L (m) must be greater than 0 and at most 10.0 m.” | Yes |
| Roof Loaded Dimension (m) | 0 to 8 mIf not: “Roof Loaded Dimension (m) must be between 0 and 8.0 m.” | No |
| Eaves Width (m) | 0 to 2 mIf not: “Eaves Width (m) must be between 0 and 2.0 m.” | No |
| Full Roof Span (m) | 0 to 12 mIf not: “Full Roof Span (m) must be between 0 and 12.0 m.” | No |
| Wall Height Above Lintel (m) | 0.3 to 4.8 mIf not: “Wall Height Above Lintel (m) must be between 0.3 m and 4.8 m.” | Yes |
| Floor Loaded Dimension (m) | 0 to 8 mIf not: “Floor Loaded Dimension (m) must be between 0 and 8.0 m.” | No |
| Full Floor Joist Span (m) | 0 to 10 mIf not: “Full Floor Joist Span (m) must be between 0 and 10.0 m.” | No |
| Supporting stud height, C (m) | 0.3 to 4 mIf not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.” | No |
- Roof TypeRequired
light · heavy
- Wall Cladding WeightRequired
light · medium · heavy
- Lower-storey wall claddingOptional
light · medium · heavy
- Beam Span, L (m)Required
more than 0 and up to 10 m
If not: “Beam Span, L (m) must be greater than 0 and at most 10.0 m.”
- Roof Loaded Dimension (m)Optional
0 to 8 m
If not: “Roof Loaded Dimension (m) must be between 0 and 8.0 m.”
- Eaves Width (m)Optional
0 to 2 m
If not: “Eaves Width (m) must be between 0 and 2.0 m.”
- Full Roof Span (m)Optional
0 to 12 m
If not: “Full Roof Span (m) must be between 0 and 12.0 m.”
- Wall Height Above Lintel (m)Required
0.3 to 4.8 m
If not: “Wall Height Above Lintel (m) must be between 0.3 m and 4.8 m.”
- Floor Loaded Dimension (m)Optional
0 to 8 m
If not: “Floor Loaded Dimension (m) must be between 0 and 8.0 m.”
- Full Floor Joist Span (m)Optional
0 to 10 m
If not: “Full Floor Joist Span (m) must be between 0 and 10.0 m.”
- Supporting stud height, C (m)Optional
0.3 to 4 m
If not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.”
Read from Lintel Supporting Roof, Wall and Floor Joists (CALC-002, version 5.0.0) as it runs today. The form may also show its own limit beside an input.
Worked example#
Here is a representative example from ArchiSuite's test suite. It is not a design for your project.
| Where | Input | Value |
|---|---|---|
| Project Settings | Wind Zone / Snow Zone | High / N1 |
| Project Settings | Elevation / Roof Pitch | 100 m / 15° |
| Project Settings | Geotechnical Ultimate Bearing Capacity | 300 kPa |
| General Info | Beam span / Supporting stud height | 3.0 m / 2.4 m |
| Roof | Roof type / Roof loaded dimension | Heavy / 3.0 m |
| Wall | Lower- / upper-storey wall cladding / Wall height above lintel | Light / Light / 2.4 m |
| Floor | Floor loaded dimension | 2.0 m |
After Analyse Beam opening, the Summary lists passing steel and timber members, including 150 PFC 17.7 (steel) and 360 x 90 hy90 (timber). With either one selected, the calculation passes, and the slab edge is adequate at both ends, so no pad footing is needed.
Results#
Summary table. Each row shows the most efficient passing member in one steel type (PFC, UB, UC) or timber group. The columns are Member Type, Most Efficient Passing Member, Max Defl Down (mm), Max Defl Up (mm), Rigidity Ratio, Capacity Ratio and Status, where the Select button is.
Floor vibration. Every member offered passes a floor vibration check: its deflection under a 1 kN point load at midspan is no more than 1.0 mm. A member that fails this check is not offered.
Show All Passing Members lists every passing size.
Foundation. The slab-edge or pad-footing results are in the calculation documents, not in the Summary table.
Support Schedule. On the drawing, the support at each end is chosen from that end's downward reaction: 2 / 90×45 studs (SG8) up to 20 kN, 3 / 90×45 studs (SG8) up to 30 kN, and a 75×5 SHS (Gr350) above 30 kN. A steel lintel is drawn on the same studs up to 24 kN uplift, at least as wide as its flange: 90, 140, 190, 240 or 290 mm (for example 2 / 140×45 studs under a 200 UB 25.4). It stands on the 75×5 SHS instead above 24 kN uplift, where its two ends need different studs, and always for a 360 UB, 250 UC, 380 PFC or larger section. The supporting stud height is printed beside it.
If no member passes, you see "No member passes - change the inputs."
Limitations#
All three loads are required. The wall height above the lintel must be at least 0.3 m, and the floor loaded dimension must be greater than 0. For a lintel with roof load only, use Lintel Supporting Roof.
The loads must be spread along the lintel. There are no inputs for point loads (such as a floor beam, girder truss or post), deck joists or a verandah.
The lintel is a single span, up to 10 m. The roof loaded dimension can be up to 8 m, the floor loaded dimension up to 8 m and the floor joist span up to 10 m.
The foundation check assumes each end sits on a concrete slab edge.
You cannot choose the member type, deflection limit, minimum bearing length (90 mm) or pad width (300 mm).
ArchiSuite does not check the supporting studs for buckling or slenderness. The height only needs to be within 0.3 to 4.0 m.
You cannot accept a design that the standard drawings do not cover (for example a timber lintel with more than 24 kN uplift).
Common errors and how to fix them#
"Roof Pitch is missing or out of range (0 - 90°) in Project Settings. Please update Project Settings to proceed." Enter a Roof Pitch between 0 and 45 degrees in Project Settings.
"Bearing Capacity is missing or out of range (150 - 300 kPa) in Project Settings. Please update Project Settings to proceed." Enter the Geotechnical Ultimate Bearing Capacity in Project Settings.
"Project Settings wind zone is required before running this calculation." (or snow zone, elevation, roof pitch, or geotechnical ultimate bearing capacity) Complete that Project Setting. See Project settings missing.
"Wall Height Above Lintel (m) must be between 0.3 m and 4.8 m." Enter the wall height between 0.3 and 4.8 m.
"Floor loaded dimension must be greater than 0." or "Roof loaded dimension must be greater than 0." Enter a value above 0 for that loaded dimension, or for its span.
"This project already has a calculation named '…'. …" Change the Calculation Name.
"No member passes - change the inputs." See No member passes.
"Project Settings changed - press Update Assessment. Changed since this calculation was assessed: …" Click Update Assessment, then select a member and accept again.
"Select a passing beam and complete the foundation check before accepting this calculation" Select a member first.
"Supporting stud height, C in section 1 (General Info) is not the saved value (…). …" Click Update Assessment to save the height, select the member again, then accept.
"This calculation cannot be accepted or issued. Beam … fails the floor vibration check: …" This can happen with a result stored before the check existed. Open the calculation, click Update Assessment and select another beam. If the calculation is paid, use Revise Calculation.
"This calculation cannot be accepted or issued. The supporting stud height is missing. …" Enter the Supporting stud height, click Update Assessment, select the member again and accept.
"… the slab edge cannot carry the load and no pad footing could be designed for it. A specific engineering design is required." See When no calculator fits.