Calculator guide · CALC-001
Lintel Supporting Roof
Size a steel or timber lintel over an opening that carries roof framing only, then check the slab edge or pad footing under each end.
On this page
Lintel Supporting Roof sizes a single-span steel or timber lintel over an opening. The lintel carries roof framing only, with no wall or floor above it. You choose one of the passing members, and ArchiSuite then checks the foundation under each end of the lintel.
Lintel Supporting Roof · CALC-001
Size a steel or timber lintel carrying roof framing, with slab-edge checks and pad footings where needed.
Use it when
- Roof framing bears on the lintel, with no wall or floor above.
- Single spans up to 10 m with evenly distributed loading.
Results
- Steel and timber member options.
- Support reactions and slab-edge or pad-footing results.
- Member and support drawing schedules.
Limits
- No point loads, cantilevers or continuous spans.
- Compression-edge restraint at 600 mm centres or closer is assumed.
- Foundation checks assume concrete slab-edge supports.
- Timber is for internal, dry use.
Before you start#
This calculator takes five values from your active project's Project Settings. You do not enter them on the form:
Wind Zone and Snow Zone
Elevation (0 to 800 m; left blank for Snow Zone N0)
Roof Pitch (0 to 45 degrees; if the roof has more than one pitch, use the lowest; not needed in Snow Zone N0)
Geotechnical Ultimate Bearing Capacity (150 to 300 kPa)
If you tick Beams & lintels under What are you designing? in Project Settings, the page shows these five fields. Save them with Update Project.
Measure these before you start:
the beam span, between the centres of the supports
the roof loaded dimension, or the eave / overhang and the full roof span
the supporting stud height, from the top of the bottom plate to the underside of the top plate
the roof type (Light or Heavy) and the wall cladding type (Light, Medium or Heavy)
Step by step#
Click All Calculators in the sidebar. Under Lintels, choose Lintel Supporting Roof.
Click New Lintel opening. If you have no lintel calculations yet, the button reads Add Lintel Calculation.
In section 1, General Info, enter a Calculation Name (for example "L1 – Garage lintel"), choose the Building storeys (Single storey unless the lintel is in the upper storey of a two-storey building), and enter the Beam span.
In section 2, Roof, choose the Roof type. Then enter either the Roof loaded dimension, or both the Eave / overhang and the Roof span. When you fill in one option, the fields of the other are greyed out.
In section 3, Wall, enter the Supporting stud height and choose the Wall cladding type. For Two storey, enter the upper-storey and the lower-storey supporting stud heights and wall cladding types. The Span and Supporting stud height sliders on the diagram set the same fields.
Click Analyse Beam opening. The Summary table appears below the form.
Fill in the three sections, then click Analyse Beam opening To see every passing size, not only the most efficient one in each type, click Show All Passing Members (optional).
Click Select on the member you want. ArchiSuite runs the calculation again for that member and checks the foundation at each end. The button changes to Selected, and you see "Beam selected successfully!".
Click Accept in the Summary header. You see "Calculation accepted successfully!", the button changes to Accepted, and the calculation is added to Project Outputs.
Select a member, then Accept
To change an input later, edit it and click Update Opening Assessment. This runs the analysis again and clears your selection, so you need to select a member and accept again. Only team admins and editors can update a calculation or select a member.
The inputs#
Click the (i) beside an input, where it appears, to open its ArchiGuide explanation.
General Info. The Beam span is the length of the lintel between its two supports. See Beam Span. The Calculation Name must be unique within the project, so the drawings and calculations can be told apart.
Roof. For Roof type, choose Light or Heavy roofing. See Roof Type. The Roof loaded dimension is the width of roof that bears on the lintel. If you don't know it, leave it blank and enter the Eave / overhang and the Roof span instead. ArchiSuite then works the loaded dimension out as the eave / overhang plus half the roof span. You do not enter the roof pitch here: it comes from Project Settings.
Wall. The Supporting stud height is the height of the studs that hold up the lintel. Measure it plate to plate, from the top of the bottom plate to the underside of the top plate. It is dimension C on the 3D model. It must be between 0.3 and 4.0 m. It is printed in the drawing's Support Schedule. It does not change the lintel design, but you cannot accept the calculation without it. The Wall cladding type sets the deflection limit and how much of the ground's capacity under the slab edge counts as already used by the house's walls. It adds no wall weight to the lintel.
Two storey. Building storeys is Single storey unless you change it. Choose Two storey where the lintel is in the upper storey of a two-storey building, so its supports stand on the mid-floor above lower-storey supports. The form then asks for four wall inputs. The Upper-storey supporting stud height and the Upper-storey wall cladding type are the two single-storey inputs, now describing the upper storey. The Lower-storey supporting stud height (0.3 to 3.0 m) and the Lower-storey wall cladding type describe the storey below. The upper-storey cladding cannot be heavier than the lower-storey cladding. Switching back to Single storey hides the lower-storey inputs, and a single-storey calculation does not use them.
In Two storey mode ArchiSuite designs the upper-storey supports, the mid-floor connection and the lower-storey supports from the selected member's reactions. Uplift is checked at the top connection, the upper-storey supports and the mid-floor connection. The lower-storey supports are designed for compression, and the foundation for bearing under the lintel's downward reaction.
| Input | Accepted values | Required |
|---|---|---|
| Roof Type | light · heavy | Yes |
| Wall cladding type | light · medium · heavy | Yes |
| Beam Span, L (m) | more than 0 and up to 10 mIf not: “Beam Span, L (m) must be greater than 0 and at most 10.0 m.” | Yes |
| Roof Loaded Dimension (m) | 0 to 8 mIf not: “Roof Loaded Dimension (m) must be between 0 and 8.0 m.” | No |
| Eaves Width (m) | 0 to 2 mIf not: “Eaves Width (m) must be between 0 and 2.0 m.” | No |
| Full Roof Span (m) | 0 to 12 mIf not: “Full Roof Span (m) must be between 0 and 12.0 m.” | No |
| Supporting stud height, C (m) | 0.3 to 4 mIf not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.” | No |
| Building storeys | single · double | No |
| Lower-storey wall cladding type | light · medium · heavy | No |
| Lower-storey supporting stud height (m)(m) | As shown on the form | No |
- Roof TypeRequired
light · heavy
- Wall cladding typeRequired
light · medium · heavy
- Beam Span, L (m)Required
more than 0 and up to 10 m
If not: “Beam Span, L (m) must be greater than 0 and at most 10.0 m.”
- Roof Loaded Dimension (m)Optional
0 to 8 m
If not: “Roof Loaded Dimension (m) must be between 0 and 8.0 m.”
- Eaves Width (m)Optional
0 to 2 m
If not: “Eaves Width (m) must be between 0 and 2.0 m.”
- Full Roof Span (m)Optional
0 to 12 m
If not: “Full Roof Span (m) must be between 0 and 12.0 m.”
- Supporting stud height, C (m)Optional
0.3 to 4 m
If not: “Design Opening Height, H (m) must be between 0.3 and 4.0 m.”
- Building storeysOptional
single · double
- Lower-storey wall cladding typeOptional
light · medium · heavy
- Lower-storey supporting stud height (m)Optional
m
Read from Lintel Supporting Roof (CALC-001, version 4.0.0) as it runs today. The form may also show its own limit beside an input.
Worked example#
Here is a representative example from ArchiSuite's test suite. It is not a design for your project.
| Where | Input | Value |
|---|---|---|
| Project Settings | Wind Zone / Snow Zone | High / N1 |
| Project Settings | Elevation / Roof Pitch | 100 m / 15° |
| Project Settings | Geotechnical Ultimate Bearing Capacity | 300 kPa |
| General Info | Beam span | 3.0 m |
| Roof | Roof type / Roof loaded dimension | Heavy / 3.0 m |
| Wall | Supporting stud height / Wall cladding type | 2.4 m / Light |
After Analyse Beam opening, the Summary lists passing steel and timber members, including 150 PFC 17.7 (steel) and 290 x 90 SG8 (timber). With either one selected, the calculation passes, and the slab edge is adequate at both ends, so no pad footing is needed. Either one can be accepted. On the drawing's Support Schedule, both stand on timber (SG8) stud supports: the 150 PFC's 75 mm flange fits a 90 mm stud.
Results#
Summary table. Each row is a steel type (PFC, UB, UC) or timber group, showing the most efficient passing member in it. The columns are Member Type, Most Efficient Passing Member, Max Defl Down (mm), Max Defl Up (mm), Rigidity Ratio, Capacity Ratio and Status, where the Select button is.
Show All Passing Members lists every passing size. After it loads, the button reads All Passing Members Loaded.
Foundation. The slab-edge or pad-footing results for each support are not shown in the Summary table. They are in the calculation documents.
Support Schedule. ArchiSuite designs the supporting studs for the lintel's reactions and the supporting stud height. On the drawing, the Support Schedule shows one support for both ends: two to four SG8 studs, in 90×45, 140×45 or either size (for example 2 / 90×45 or 2 / 140×45 studs). Under a steel lintel the studs are at least as wide as its flange (for example 2 / 140×45 studs under a 200 UB 25.4). A steel lintel stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate, where the downward reaction at a support is over 50 kN, where the uplift is over 24 kN, and always for a 360 UB, 250 UC, 380 PFC or larger section. The supporting stud height is printed beside the support. A calculation accepted before the studs were designed this way keeps the support it was accepted with.
Two storey. The upper-storey supports, the mid-floor connection and the lower-storey supports are not shown in the Summary table. They are in the calculation documents, the drawing and the Project Summary.
If no member passes, you see "No member passes - change the inputs." instead of the table.
Limitations#
The lintel carries roof load only. The form has no inputs for a wall, floor, girder truss or post load on the lintel. If a wall and floor joists also bear on it, use Lintel Supporting Roof, Wall & Floor Joists.
The lintel is a single span, up to 10 m. The roof loaded dimension can be up to 8 m, the eave / overhang up to 2 m and the roof span up to 12 m.
The foundation check assumes each end sits on a concrete slab edge.
You cannot choose the member type, deflection limit, minimum bearing length (90 mm) or pad width (300 mm). Every passing steel and timber member is offered.
The supporting stud height must be between 0.3 and 4.0 m. ArchiSuite checks the supporting studs, and the SHS post where one is used, for buckling at that height. The studs are checked with rows of dwangs at 1350 mm centres or closer, as the drawing notes.
The supports are SG8 studs, 90×45 or 140×45, two to four to a support, or the 75×5 SHS post under a steel lintel. You cannot choose the stud grade, size or number.
Two storey: the lower-storey supports are two to four full-height timber studs, carrying up to 50 kN, and are never shallower than the upper-storey studs. The lower-storey supporting stud height must be between 0.3 and 3.0 m. Where no standard support or mid-floor connection covers the design, it needs a specific engineering design and cannot be accepted.
You cannot accept a design that the standard drawings do not cover. Examples: a timber lintel with more than 24 kN uplift or more than 50 kN downward reaction at a support, or any lintel with more than 30 kN uplift.
Common errors and how to fix them#
"Roof Pitch is missing or out of range (0 - 90°) in Project Settings. Please update Project Settings to proceed." Enter a Roof Pitch between 0 and 45 degrees in Project Settings and click Update Project.
"Bearing Capacity is missing or out of range (150 - 300 kPa) in Project Settings. Please update Project Settings to proceed." Enter the Geotechnical Ultimate Bearing Capacity (150 to 300 kPa) in Project Settings.
"Project Settings wind zone is required before running this calculation." (or snow zone, elevation, roof pitch, or geotechnical ultimate bearing capacity) Complete that field in Project Settings, then analyse again. See Project settings missing.
"Roof loaded dimension must be greater than 0." Enter a roof loaded dimension above 0, or a roof span above 0.
"This project already has a calculation named '…'. Give this one a different name, so its drawings and calculations can be told apart." Change the Calculation Name.
"No member passes - change the inputs." No steel or timber member passes every check. Try a shorter span or a smaller loaded dimension, or see No member passes.
"Project Settings changed - press Update Assessment. Changed since this calculation was assessed: …" Click Update Opening Assessment, then select a member and accept again.
"Select a passing beam and complete the foundation check before accepting this calculation" Click Select on a member first.
"Supporting stud height, C in section 3 (Wall) is not the saved value (…). Save it with the "Update Opening Assessment" button, select the member again, then accept." The height on screen has not been saved. Click Update Opening Assessment, select the member again, then accept.
"Lower-storey wall cladding type is required for a two-storey design." Choose the Lower-storey wall cladding type, or set Building storeys back to Single storey.
"Lower-storey supporting stud height (m) must be between 0.3 and 3.0 m." Enter a lower-storey supporting stud height within that range. The form shows "Allowed range: 0.3 – 3.0 m".
"Upper cladding mass cannot exceed lower cladding mass as per NZS 3604:2011 Tables 5.9 and 5.10." Choose a lower-storey wall cladding type at least as heavy as the upper-storey one.
"Building storeys in section 1 (General Info) is not the saved value (…). Save it with the "Update Opening Assessment" button, which analyses the calculation again, select the member again, then accept." The storey mode on screen has not been saved. The same message names the Lower-storey supporting stud height or the Lower-storey wall cladding type when that is the unsaved input. Click Update Opening Assessment, select the member again, then accept.
"This calculation cannot be accepted or issued. The supporting stud height is missing. …" Enter the Supporting stud height, click Update Opening Assessment, select the member again and accept. A paid calculation is locked, so change it through Revise Calculation.
"… Support A: the slab edge cannot carry the load and no pad footing could be designed for it. A specific engineering design is required." The foundation cannot be designed for this case. See When no calculator fits.
"… No standard ArchiSuite detail covers this design: Timber lintel drawings stop at 24 kN uplift. Select and recalculate a passing steel member before issuing the drawing." Select a passing steel member instead, then accept.