Worked example · CALC-027
How to Use the Floor Beam Calculator: Worked Example
A step-by-step worked example of the Floor Beam Supporting Floor calculator, with a screen-recorded video - a 4.0 m beam carrying a timber floor, from Project Settings to the accepted calculation.
- Author
- ArchiSuite
- Technical review:
- Michael Sheridan
- Reviewed:
- Published:
On this page
This worked example takes one real design through the Floor Beam Supporting Floor calculator, from Project Settings to an accepted calculation in Project Outputs. The calculator sizes a single-span steel or timber beam that carries timber floor joists, and nothing else, then checks the foundation under each end. Every value below was entered in ArchiSuite, and every result was read from it.
Video tutorial#
The example project#
A load-bearing internal wall on the ground floor of a two-storey house is being replaced with a beam, to open the living room into the dining room. The wall carries only the timber first floor: no roof, wall or point loads come down onto it. The beam spans 4.0 m between new posts, and the first-floor joists span 3.0 m onto it from each side at 450 mm centres.
What the example assumes:
The beam carries floor load only. There is no roof, wall or point load on it.
It is a single span, simply supported on a post at each end, inside the building.
Each end of the beam sits on the edge of the concrete ground-floor slab, which is what the foundation check assumes.
The calculator does not check building bracing. If the wall being removed is a bracing wall, the lost bracing has to be replaced and designed separately.
The values are an illustration. They are not defaults for your project.
Step 1: Open the calculator#
Make the project active. Its name is shown under Active project at the top of every page.
Click All Calculators in the sidebar.
Under Floor Beams, choose Floor Beam Supporting Floor.
Click Add Floor Beam Calculation, or New Floor Beam calculation once the project has one.
Step 2: Check the project information#
The calculator reads one value from the active project's Project Settings:
| Project Setting | Value used | Unit | Why it matters here |
|---|---|---|---|
| Geotechnical Ultimate Bearing Capacity | 300 | kPa | The only Project Setting this calculator reads. It is used in the foundation check under each end of the beam. 300 kPa is the ultimate bearing pressure that good ground must withstand under NZS 3604; use your own site's value. |
With Beams & lintels selected under What are you designing?, Project Settings also asks for a wind zone and a snow zone (and, outside snow zone N0, the elevation and roof pitch), because other beam and lintel calculators use them. The Floor Beam Supporting Floor calculator does not use them.
Step 3: Enter the beam design inputs#
The form has three sections. The arrangement diagram above it redraws the span and the supporting stud height as you type.
These are the exact values entered in the recording:
| Section | Field | Value used | Unit | What it means |
|---|---|---|---|---|
| General Info | Calculation Name | FB1 - Living room floor beam | - | Names the calculation in Project Outputs and on the drawings and calculations. Each calculation in a project needs its own name. |
| General Info | Beam span | 4.0 | m | The length of the beam between its supports. The form accepts 0.1 to 10.0 m. |
| General Info | Supporting stud height | 2.4 | m | From the floor or slab to the underside of the beam at a post. ArchiSuite designs the supporting studs for this height and prints it in the drawing's Support Schedule; it does not change the beam design. The form accepts 0.3 to 4.0 m. |
| Floor | Floor type | Timber Floor | - | Sets the floor weight and live load. Timber Floor, already selected, is for an internal timber floor: the calculation uses G = 0.40 kPa and Q = 1.50 kPa. |
| Floor | Floor loaded dimension | 3.0 | m | The width of floor the beam carries: half the joist span on each side, added together. With 3.0 m joists on both sides it is 1.5 m + 1.5 m = 3.0 m. Enter this or the Full floor joist span, not both. |
| Floor | Full floor joist span | (left blank) | m | Left blank. It is the alternative to the floor loaded dimension: both joist spans together (here it would be 6.0 m), which ArchiSuite halves. The field greys out once a loaded dimension is entered. |
| Floor | Joist spacing | 0.45 | m | The spacing of the floor joists fixed on top of the beam. They hold the beam's top edge, so ArchiSuite treats it as restrained at this spacing. The form accepts 0.1 to 0.6 m. |
| Building weights | Roof weight | Light roof | - | The building's roof: Light roof or Heavy roof. Used only in the foundation check under each end of the beam. It adds no load to the beam. |
| Building weights | Lower-storey wall cladding | Light cladding | - | The ground-floor wall cladding: Light, Medium or Heavy. With the roof weight, it sets how much of the ground's capacity the building already uses in the foundation check. It adds no load to the beam. |
| Building weights | Upper-storey wall cladding | Light cladding | - | The first-floor wall cladding. It cannot be heavier than the lower storey's. Used only in the foundation check. |
Step 4: Run the calculation#
Click Analyse Floor Beam. The button shows Processing… while the calculation runs, and the Summary table then appears below the form. If an input is missing or out of range, the form says so beside the field and does not submit.
Step 5: Understand the results#
The Summary#
The Summary lists the most efficient passing member of each member type: three steel sections and eleven engineered timber groups. These are the values ArchiSuite showed for this example. The member selected below is in bold.
| Member Type | Material | Most Efficient Passing Member | Max Defl Down (mm) | Max Defl Up (mm) | Rigidity Ratio | Capacity Ratio |
|---|---|---|---|---|---|---|
| PFC | Steel | 150 PFC 17.7 | 9.04 | 0.00 | 1.251 | 1.903 |
| UB | Steel | 150 UB 18 | 8.34 | 0.00 | 1.357 | 1.997 |
| UC | Steel | 150 UC 23.4 | 6.01 | 0.00 | 1.905 | 2.841 |
| HY90 | Timber | 300 x 90 hy90 | 10.96 | 0.00 | 1.216 | 1.651 |
| HYSPAN | Timber | 300 x 63 hySPAN | 11.10 | 0.00 | 1.201 | 1.711 |
| HYONE | Timber | 240 x 90 hyONE | 12.58 | 0.00 | 1.059 | 2.100 |
| LVL11 | Timber | 360 x 45 LVL11 | 10.72 | 0.00 | 1.244 | 1.262 |
| LVL13 | Timber | 300 x 63 LVL13 | 11.09 | 0.00 | 1.203 | 1.619 |
| GL8 | Timber | 315 x 88 GL8 | 11.45 | 0.00 | 1.164 | 1.049 |
| GL10 | Timber | 360 x 65 GL10 | 8.25 | 0.00 | 1.617 | 1.149 |
| GL12 | Timber | 315 x 65 GL12 | 10.65 | 0.00 | 1.252 | 1.025 |
| PROLAM PL8 | Timber | 315 x 88 Prolam PL8 | 11.45 | 0.00 | 1.164 | 1.049 |
| PROLAM PL12 | Timber | 290 x 88 Prolam PL12 | 10.17 | 0.00 | 1.311 | 1.181 |
| PROLAM PL17 | Timber | 240 x 88 Prolam PL17 | 12.26 | 0.00 | 1.087 | 1.364 |
What the columns mean:
Max Defl Down (mm) and Max Defl Up (mm) are the member's largest calculated deflections, down and up, in millimetres.
Rigidity Ratio is the smallest of the member's stiffness checks, each one limit ÷ calculated value: the deflection checks and the floor vibration check (the deflection under a 1 kN load at midspan, limited to 1.0 mm).
Capacity Ratio is the smallest of its strength checks, each one capacity ÷ demand, for bending and shear.
A ratio of 1.0 or more passes. Every row in the Summary passes all of these checks. A member that fails one, including floor vibration, is not offered.
Show All Passing Members lists every passing size, not only the most efficient of each type.
Selecting a member#
The example selects 150 PFC 17.7. It is the first row: the most efficient passing PFC (steel channel) and, at 17.7 kg/m, the lightest steel member in the Summary. Choose the member that suits your project: every row in the Summary passes the calculator’s checks.
Click Select on its row. ArchiSuite runs the calculation again for that member and checks the foundation under each end, then shows:
The selected member's results#
These are the results ArchiSuite stored for 150 PFC 17.7:
| Result | Value |
|---|---|
| Selected member | 150 PFC 17.7 |
| Result | Pass |
| Floor dead load G | 0.40 kPa |
| Floor live load Q | 1.50 kPa |
| Floor dead line load on the beam | 1.20 kN/m |
| Floor live line load on the beam | 4.50 kN/m |
| Maximum bending moment M* | 16.80 kNm |
| Maximum shear V* | 16.80 kN |
| Reaction at each end (ULS) | 16.80 kN |
| Uplift at each end | 0.00 kN |
| Maximum deflection (service) | 9.04 mm |
| Existing slab edge adequate | Yes |
| Slab-edge bearing length required | 673 mm |
Strength and serviceability checks#
The Structural Calculations document for this example lists its governing checks. Utilisation is demand ÷ capacity or limit, so it is the inverse of the ratios in the Summary: the floor vibration utilisation of 0.80 is the Rigidity Ratio of 1.251, and the bending utilisation of 0.53 is the Capacity Ratio of 1.903.
| Part | Check | Demand | Capacity or limit | Utilisation |
|---|---|---|---|---|
| Floor beam | Bending, sagging ([FLOOR 1.2G + 1.5Q]) | 16.80 kNm | 31.97 kNm | 0.53 |
| Floor beam | Shear (ULS) | 16.80 kN | 135.82 kN | 0.12 |
| Floor beam | Deflection, FLOOR SLS SHORT: G + 0.7Qf (L/300) | 9.04 mm | 13.33 mm | 0.68 |
| Floor beam | Floor vibration (1 kN at midspan) – governs | 0.799 mm | 1.000 mm | 0.80 |
| Supporting studs | 2 / 90×45 studs: compression (bending and compression (eq 3.23), [FLOOR 1.2G + 1.5Q]) – governs | 16.80 kN | 20.29 kN | 0.83 |
| Supporting studs | 2 / 140×45 studs: compression (bending and compression (eq 3.24), [FLOOR 1.2G + 1.5Q]) | 16.80 kN | 47.01 kN | 0.36 |
| Slab edge (option 1) | Bending (bearing or uplift length) | 2.55 kNm | 23.23 kNm | 0.11 |
| Slab edge (option 1) | Shear (bearing or uplift length) – governs | 15.14 kN | 30.77 kN | 0.49 |
| Slab edge (option 1) | Bearing length towards the other support (L/2) | 336 mm | 3664 mm | 0.09 |
| Pad footing (option 2) | Bearing pressure (1.2G; 1.5Q) – governs | 145.8 kPa | 150.0 kPa | 0.97 |
| Pad footing (option 2) | Punching shear (1.2G; 1.5Q) | 0.084 MPa | 1.571 MPa | 0.05 |
| Pad footing (option 2) | Beam shear (1.2G; 1.5Q) | 0.151 MPa | 0.800 MPa | 0.19 |
| Pad footing (option 2) | Bending (1.2G; 1.5Q) | 0.78 kNm | 14.78 kNm | 0.05 |
The document's conclusion:
The two foundation options are alternatives at each end: the document checks the existing slab edge (here with 2-HD12 enhancement steel and a 673 mm bearing length) and, separately, a 350 × 350 × 300 mm pad footing. Build either adequate option.
Warnings and limitations#
The calculation states its own scope: "Isolated single-span simply supported floor beams only — not continuous bearers, two-span NZS 3604 bearers, cantilevers, deck/balcony/veranda beams or wet-in-service framing."
"Beam-to-support connection design is required separately (reactions are reported; no connection is claimed to pass)."
ArchiSuite designs the supporting studs under the beam for its reactions and the supporting stud height, and checks them for buckling at that height. The Support Schedule on the drawings shows one support for both ends: two to four SG8 studs in 90×45, 140×45 or either size (here 2 / 90×45 or 2 / 140×45 studs). A steel beam stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate or the downward reaction at a support is over 50 kN.
The Building weights add no load to the beam. They are used only in the foundation check.
Step 6: Access the documentation#
Click Accept in the Summary header. ArchiSuite shows:
Open Project Outputs from the sidebar. The calculation is listed under Accepted calculator outputs included with its status.
What you can see and download, and when:
On screen. The Summary, the selected member and its pass status are in the calculator itself, as soon as you analyse and select.
The document packs. Project Outputs offers three PDFs: the Project Summary, the Structural Calculations (every calculation page, including the governing checks and foundation details above) and the Structural Drawings. They download once every accepted output is paid.
Documents that wait for review. Where an Engineering Review is included (it always is for an account without a Licensed Building Practitioner number), the downloads also wait until ArchiSuite has reviewed the documents and released them for issue. See Pay and download your documents.
Once the review is released, the panel says so and every download opens.
The video ends with a quick look through the documents this example produced, as issued: the Project Summary; the PS1 Producer Statement - Design and its Schedule, shown unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; every page of the Structural Calculations; and every sheet of the Structural Drawings.
Common mistakes#
Entering both floor fields. Enter the Floor loaded dimension or the Full floor joist span. The other field greys out once one has a value. If neither is filled in, the calculator refuses with "Please enter either Floor Loaded Dimension / Tributary OR Full Floor Joist Span."
Halving twice. The full floor joist span is both joist spans together, which ArchiSuite halves. If you enter a loaded dimension yourself, it is already the half-spans added together.
The wrong floor type. Timber Floor is for an internal timber floor. The calculator is not for deck, balcony or veranda beams.
A heavier upper storey. The upper-storey wall cladding cannot be heavier than the lower storey's. The form says so and will not submit.
No bearing capacity. Without the Geotechnical Ultimate Bearing Capacity in Project Settings, the calculator refuses with "Project Settings geotechnical ultimate bearing capacity is required before running this calculation." See Project settings missing.
Editing after selecting. Changing an input and clicking Update Assessment clears your selection: select the member and accept again.
The same name twice. Each calculation in a project needs its own name. Leaving the name blank on a second floor beam gives both the default name, which is refused.
Nothing passes. "No member passes - change the inputs." See No member passes.
Related guides#
Floor Beam Supporting Floor: every input, result and refusal of this calculator.
Open the calculator: Floor Beam Supporting Floor (signed in).
The inputs explained: Beam Span, Floor type, Floor loaded dimension, Joist spacing, Geotechnical Ultimate Bearing Capacity, Roof Type and Wall Cladding Weight.
Project Settings, Check and accept results and Pay and download your documents.
Building & Engineering: What is "good ground" under NZS 3604? and When do you need a structural engineer?
Engineering note#
Recorded with CALC-027 Floor Beam Supporting Floor version 4.0.0 on 2026-11-25.
Video transcript#
0:07 The project Worked Example - Floor Beam is active. In Project Settings, the Geotechnical Ultimate Bearing Capacity is 300 kPa: the only Project Setting the Floor Beam Supporting Floor calculator reads.
0:17 Under All Calculators, in Floor Beams, open Floor Beam Supporting Floor, then Add Floor Beam Calculation. The calculator sizes a single-span steel or timber beam that carries timber floor joists only.
0:27 The form has three sections: General Info, Floor and Building weights. The arrangement diagram above it follows the values as you type.
0:31 In General Info, the calculation is named FB1 - Living room floor beam. The Beam span is 4.0 m, the length between the supports. The Supporting stud height is 2.4 m, from the floor to the underside of the beam at a post.
0:44 In Floor, Timber Floor is already selected. The Floor loaded dimension is 3.0 m: the joists span 3.0 m onto the beam from each side, so it carries half of each, 1.5 m plus 1.5 m. The Full floor joist span is left blank and greys out. The Joist spacing is 0.45 m.
0:56 In Building weights, Light roof, Light cladding for the lower storey and Light cladding for the upper storey are chosen. They are used only in the foundation check under each end of the beam and add no load to the beam.
1:09 Analyse Floor Beam runs the calculation. When it finishes, the Summary lists the most efficient passing member of each member type.
1:17 Every row passes. Max Defl Down and Max Defl Up are the beam's largest deflections, in millimetres. The Rigidity Ratio is the smallest of the deflection and floor vibration checks, limit divided by result; the Capacity Ratio is the smallest strength check, capacity divided by demand, for bending and shear. Both must be at least 1.0. The first row, 150 PFC 17.7, deflects 9.04 mm and has a Rigidity Ratio of 1.251 and a Capacity Ratio of 1.903. Show All Passing Members lists every size that passes.
1:39 Select on the 150 PFC 17.7 row selects that member. ArchiSuite runs the calculation again for it, checks the foundations and shows a confirmation. Accept then adds the calculation to Project Outputs.
1:49 Project Outputs lists FB1 - Living room floor beam as an accepted output. The Structural Calculations and Structural Drawings, with the full checks and the foundation details, download from here once the outputs are paid and, where Engineering Review is included, reviewed and released. Prices are hidden in this video.
2:01 After payment and Engineering Review (not shown), Project Outputs shows the document packs ready to download. A quick look through what they contain: the Project Summary, with the project and every accepted calculation; the PS1 Producer Statement - Design and its Schedule, shown here unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; the Structural Calculations; and the Structural Drawings.