Worked example · CALC-027

How to Use the Floor Beam Calculator: Worked Example

A step-by-step worked example of the Floor Beam Supporting Floor calculator, with a screen-recorded video - a 4.0 m beam carrying a timber floor, from Project Settings to the accepted calculation.

Author
ArchiSuite
Technical review:
Michael Sheridan
Reviewed:
Published:
On this page

This worked example takes one real design through the Floor Beam Supporting Floor calculator, from Project Settings to an accepted calculation in Project Outputs. The calculator sizes a single-span steel or timber beam that carries timber floor joists, and nothing else, then checks the foundation under each end. Every value below was entered in ArchiSuite, and every result was read from it.

Video tutorial#

The whole example, including a quick look at its documents, in about three minutes. Each step is captioned on screen; closed captions (CC) and the transcript at the end of this page give the same steps as text.2:57Read the transcript

The example project#

A load-bearing internal wall on the ground floor of a two-storey house is being replaced with a beam, to open the living room into the dining room. The wall carries only the timber first floor: no roof, wall or point loads come down onto it. The beam spans 4.0 m between new posts, and the first-floor joists span 3.0 m onto it from each side at 450 mm centres.

What the example assumes:

  • The beam carries floor load only. There is no roof, wall or point load on it.

  • It is a single span, simply supported on a post at each end, inside the building.

  • Each end of the beam sits on the edge of the concrete ground-floor slab, which is what the foundation check assumes.

  • The calculator does not check building bracing. If the wall being removed is a bracing wall, the lost bracing has to be replaced and designed separately.

  • The values are an illustration. They are not defaults for your project.

Step 1: Open the calculator#

  1. Make the project active. Its name is shown under Active project at the top of every page.

  2. Click All Calculators in the sidebar.

  3. Under Floor Beams, choose Floor Beam Supporting Floor.

  4. Click Add Floor Beam Calculation, or New Floor Beam calculation once the project has one.

All Calculators: Floor Beams → Floor Beam Supporting Floor

Step 2: Check the project information#

The calculator reads one value from the active project's Project Settings:

Project SettingValue usedUnitWhy it matters here
Geotechnical Ultimate Bearing Capacity300kPaThe only Project Setting this calculator reads. It is used in the foundation check under each end of the beam. 300 kPa is the ultimate bearing pressure that good ground must withstand under NZS 3604; use your own site's value.

With Beams & lintels selected under What are you designing?, Project Settings also asks for a wind zone and a snow zone (and, outside snow zone N0, the elevation and roof pitch), because other beam and lintel calculators use them. The Floor Beam Supporting Floor calculator does not use them.

Project Settings: the bearing capacity is the only setting this calculator reads

Step 3: Enter the beam design inputs#

The form has three sections. The arrangement diagram above it redraws the span and the supporting stud height as you type.

The new calculation, before any inputs

These are the exact values entered in the recording:

SectionFieldValue usedUnitWhat it means
General InfoCalculation NameFB1 - Living room floor beam-Names the calculation in Project Outputs and on the drawings and calculations. Each calculation in a project needs its own name.
General InfoBeam span4.0mThe length of the beam between its supports. The form accepts 0.1 to 10.0 m.
General InfoSupporting stud height2.4mFrom the floor or slab to the underside of the beam at a post. ArchiSuite designs the supporting studs for this height and prints it in the drawing's Support Schedule; it does not change the beam design. The form accepts 0.3 to 4.0 m.
FloorFloor typeTimber Floor-Sets the floor weight and live load. Timber Floor, already selected, is for an internal timber floor: the calculation uses G = 0.40 kPa and Q = 1.50 kPa.
FloorFloor loaded dimension3.0mThe width of floor the beam carries: half the joist span on each side, added together. With 3.0 m joists on both sides it is 1.5 m + 1.5 m = 3.0 m. Enter this or the Full floor joist span, not both.
FloorFull floor joist span(left blank)mLeft blank. It is the alternative to the floor loaded dimension: both joist spans together (here it would be 6.0 m), which ArchiSuite halves. The field greys out once a loaded dimension is entered.
FloorJoist spacing0.45mThe spacing of the floor joists fixed on top of the beam. They hold the beam's top edge, so ArchiSuite treats it as restrained at this spacing. The form accepts 0.1 to 0.6 m.
Building weightsRoof weightLight roof-The building's roof: Light roof or Heavy roof. Used only in the foundation check under each end of the beam. It adds no load to the beam.
Building weightsLower-storey wall claddingLight cladding-The ground-floor wall cladding: Light, Medium or Heavy. With the roof weight, it sets how much of the ground's capacity the building already uses in the foundation check. It adds no load to the beam.
Building weightsUpper-storey wall claddingLight cladding-The first-floor wall cladding. It cannot be heavier than the lower storey's. Used only in the foundation check.
The completed inputs for FB1 - Living room floor beam

Step 4: Run the calculation#

Click Analyse Floor Beam. The button shows Processing… while the calculation runs, and the Summary table then appears below the form. If an input is missing or out of range, the form says so beside the field and does not submit.

Step 5: Understand the results#

The Summary#

The Summary lists the most efficient passing member of each member type: three steel sections and eleven engineered timber groups. These are the values ArchiSuite showed for this example. The member selected below is in bold.

Member TypeMaterialMost Efficient Passing MemberMax Defl Down (mm)Max Defl Up (mm)Rigidity RatioCapacity Ratio
PFCSteel150 PFC 17.79.040.001.2511.903
UBSteel150 UB 188.340.001.3571.997
UCSteel150 UC 23.46.010.001.9052.841
HY90Timber300 x 90 hy9010.960.001.2161.651
HYSPANTimber300 x 63 hySPAN11.100.001.2011.711
HYONETimber240 x 90 hyONE12.580.001.0592.100
LVL11Timber360 x 45 LVL1110.720.001.2441.262
LVL13Timber300 x 63 LVL1311.090.001.2031.619
GL8Timber315 x 88 GL811.450.001.1641.049
GL10Timber360 x 65 GL108.250.001.6171.149
GL12Timber315 x 65 GL1210.650.001.2521.025
PROLAM PL8Timber315 x 88 Prolam PL811.450.001.1641.049
PROLAM PL12Timber290 x 88 Prolam PL1210.170.001.3111.181
PROLAM PL17Timber240 x 88 Prolam PL1712.260.001.0871.364
The Summary after Analyse Floor Beam

What the columns mean:

  • Max Defl Down (mm) and Max Defl Up (mm) are the member's largest calculated deflections, down and up, in millimetres.

  • Rigidity Ratio is the smallest of the member's stiffness checks, each one limit ÷ calculated value: the deflection checks and the floor vibration check (the deflection under a 1 kN load at midspan, limited to 1.0 mm).

  • Capacity Ratio is the smallest of its strength checks, each one capacity ÷ demand, for bending and shear.

  • A ratio of 1.0 or more passes. Every row in the Summary passes all of these checks. A member that fails one, including floor vibration, is not offered.

  • Show All Passing Members lists every passing size, not only the most efficient of each type.

Selecting a member#

The example selects 150 PFC 17.7. It is the first row: the most efficient passing PFC (steel channel) and, at 17.7 kg/m, the lightest steel member in the Summary. Choose the member that suits your project: every row in the Summary passes the calculator’s checks.

Click Select on its row. ArchiSuite runs the calculation again for that member and checks the foundation under each end, then shows:

After Select, the row shows SELECTED

The selected member's results#

These are the results ArchiSuite stored for 150 PFC 17.7:

ResultValue
Selected member150 PFC 17.7
ResultPass
Floor dead load G0.40 kPa
Floor live load Q1.50 kPa
Floor dead line load on the beam1.20 kN/m
Floor live line load on the beam4.50 kN/m
Maximum bending moment M*16.80 kNm
Maximum shear V*16.80 kN
Reaction at each end (ULS)16.80 kN
Uplift at each end0.00 kN
Maximum deflection (service)9.04 mm
Existing slab edge adequateYes
Slab-edge bearing length required673 mm

Strength and serviceability checks#

The Structural Calculations document for this example lists its governing checks. Utilisation is demand ÷ capacity or limit, so it is the inverse of the ratios in the Summary: the floor vibration utilisation of 0.80 is the Rigidity Ratio of 1.251, and the bending utilisation of 0.53 is the Capacity Ratio of 1.903.

PartCheckDemandCapacity or limitUtilisation
Floor beamBending, sagging ([FLOOR 1.2G + 1.5Q])16.80 kNm31.97 kNm0.53
Floor beamShear (ULS)16.80 kN135.82 kN0.12
Floor beamDeflection, FLOOR SLS SHORT: G + 0.7Qf (L/300)9.04 mm13.33 mm0.68
Floor beamFloor vibration (1 kN at midspan) – governs0.799 mm1.000 mm0.80
Supporting studs2 / 90×45 studs: compression (bending and compression (eq 3.23), [FLOOR 1.2G + 1.5Q]) – governs16.80 kN20.29 kN0.83
Supporting studs2 / 140×45 studs: compression (bending and compression (eq 3.24), [FLOOR 1.2G + 1.5Q])16.80 kN47.01 kN0.36
Slab edge (option 1)Bending (bearing or uplift length)2.55 kNm23.23 kNm0.11
Slab edge (option 1)Shear (bearing or uplift length) – governs15.14 kN30.77 kN0.49
Slab edge (option 1)Bearing length towards the other support (L/2)336 mm3664 mm0.09
Pad footing (option 2)Bearing pressure (1.2G; 1.5Q) – governs145.8 kPa150.0 kPa0.97
Pad footing (option 2)Punching shear (1.2G; 1.5Q)0.084 MPa1.571 MPa0.05
Pad footing (option 2)Beam shear (1.2G; 1.5Q)0.151 MPa0.800 MPa0.19
Pad footing (option 2)Bending (1.2G; 1.5Q)0.78 kNm14.78 kNm0.05

The document's conclusion:

The two foundation options are alternatives at each end: the document checks the existing slab edge (here with 2-HD12 enhancement steel and a 673 mm bearing length) and, separately, a 350 × 350 × 300 mm pad footing. Build either adequate option.

Warnings and limitations#

  • The calculation states its own scope: "Isolated single-span simply supported floor beams only — not continuous bearers, two-span NZS 3604 bearers, cantilevers, deck/balcony/veranda beams or wet-in-service framing."

  • "Beam-to-support connection design is required separately (reactions are reported; no connection is claimed to pass)."

  • ArchiSuite designs the supporting studs under the beam for its reactions and the supporting stud height, and checks them for buckling at that height. The Support Schedule on the drawings shows one support for both ends: two to four SG8 studs in 90×45, 140×45 or either size (here 2 / 90×45 or 2 / 140×45 studs). A steel beam stands on a 75×5 SHS (Gr350) post instead where neither stud size is adequate or the downward reaction at a support is over 50 kN.

  • The Building weights add no load to the beam. They are used only in the foundation check.

Step 6: Access the documentation#

  1. Click Accept in the Summary header. ArchiSuite shows:

  1. Open Project Outputs from the sidebar. The calculation is listed under Accepted calculator outputs included with its status.

Project Outputs lists the accepted calculation (prices blurred)

What you can see and download, and when:

  • On screen. The Summary, the selected member and its pass status are in the calculator itself, as soon as you analyse and select.

  • The document packs. Project Outputs offers three PDFs: the Project Summary, the Structural Calculations (every calculation page, including the governing checks and foundation details above) and the Structural Drawings. They download once every accepted output is paid.

  • Documents that wait for review. Where an Engineering Review is included (it always is for an account without a Licensed Building Practitioner number), the downloads also wait until ArchiSuite has reviewed the documents and released them for issue. See Pay and download your documents.

The document packs open after payment and, where included, Engineering Review

Once the review is released, the panel says so and every download opens.

After payment and Engineering Review: the documents are released for issue

The video ends with a quick look through the documents this example produced, as issued: the Project Summary; the PS1 Producer Statement - Design and its Schedule, shown unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; every page of the Structural Calculations; and every sheet of the Structural Drawings.

Common mistakes#

  • Entering both floor fields. Enter the Floor loaded dimension or the Full floor joist span. The other field greys out once one has a value. If neither is filled in, the calculator refuses with "Please enter either Floor Loaded Dimension / Tributary OR Full Floor Joist Span."

  • Halving twice. The full floor joist span is both joist spans together, which ArchiSuite halves. If you enter a loaded dimension yourself, it is already the half-spans added together.

  • The wrong floor type. Timber Floor is for an internal timber floor. The calculator is not for deck, balcony or veranda beams.

  • A heavier upper storey. The upper-storey wall cladding cannot be heavier than the lower storey's. The form says so and will not submit.

  • No bearing capacity. Without the Geotechnical Ultimate Bearing Capacity in Project Settings, the calculator refuses with "Project Settings geotechnical ultimate bearing capacity is required before running this calculation." See Project settings missing.

  • Editing after selecting. Changing an input and clicking Update Assessment clears your selection: select the member and accept again.

  • The same name twice. Each calculation in a project needs its own name. Leaving the name blank on a second floor beam gives both the default name, which is refused.

  • Nothing passes. "No member passes - change the inputs." See No member passes.

Engineering note#

Recorded with CALC-027 Floor Beam Supporting Floor version 4.0.0 on 2026-11-25.

Video transcript#

  • 0:07 The project Worked Example - Floor Beam is active. In Project Settings, the Geotechnical Ultimate Bearing Capacity is 300 kPa: the only Project Setting the Floor Beam Supporting Floor calculator reads.

  • 0:17 Under All Calculators, in Floor Beams, open Floor Beam Supporting Floor, then Add Floor Beam Calculation. The calculator sizes a single-span steel or timber beam that carries timber floor joists only.

  • 0:27 The form has three sections: General Info, Floor and Building weights. The arrangement diagram above it follows the values as you type.

  • 0:31 In General Info, the calculation is named FB1 - Living room floor beam. The Beam span is 4.0 m, the length between the supports. The Supporting stud height is 2.4 m, from the floor to the underside of the beam at a post.

  • 0:44 In Floor, Timber Floor is already selected. The Floor loaded dimension is 3.0 m: the joists span 3.0 m onto the beam from each side, so it carries half of each, 1.5 m plus 1.5 m. The Full floor joist span is left blank and greys out. The Joist spacing is 0.45 m.

  • 0:56 In Building weights, Light roof, Light cladding for the lower storey and Light cladding for the upper storey are chosen. They are used only in the foundation check under each end of the beam and add no load to the beam.

  • 1:09 Analyse Floor Beam runs the calculation. When it finishes, the Summary lists the most efficient passing member of each member type.

  • 1:17 Every row passes. Max Defl Down and Max Defl Up are the beam's largest deflections, in millimetres. The Rigidity Ratio is the smallest of the deflection and floor vibration checks, limit divided by result; the Capacity Ratio is the smallest strength check, capacity divided by demand, for bending and shear. Both must be at least 1.0. The first row, 150 PFC 17.7, deflects 9.04 mm and has a Rigidity Ratio of 1.251 and a Capacity Ratio of 1.903. Show All Passing Members lists every size that passes.

  • 1:39 Select on the 150 PFC 17.7 row selects that member. ArchiSuite runs the calculation again for it, checks the foundations and shows a confirmation. Accept then adds the calculation to Project Outputs.

  • 1:49 Project Outputs lists FB1 - Living room floor beam as an accepted output. The Structural Calculations and Structural Drawings, with the full checks and the foundation details, download from here once the outputs are paid and, where Engineering Review is included, reviewed and released. Prices are hidden in this video.

  • 2:01 After payment and Engineering Review (not shown), Project Outputs shows the document packs ready to download. A quick look through what they contain: the Project Summary, with the project and every accepted calculation; the PS1 Producer Statement - Design and its Schedule, shown here unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; the Structural Calculations; and the Structural Drawings.

Was this helpful?

Calculator guideFloor Beam Supporting FloorSize a steel or timber beam that carries internal timber floor joists only, with a floor vibration check and slab-edge or pad checks under each end.Read Worked exampleHow to Use the Roof Beam Calculator: Worked ExampleA step-by-step worked example of the Roof Beam Supporting Roof Framing/Trusses calculator, with a screen-recorded video - a 4.2 m timber roof beam under a light roof, including wind uplift, from Project Settings to the accepted calculation.Read How-toProject SettingsEvery field on the Project Settings page - what it means, the accepted options and limits, which calculators use it, and what happens to existing calculations when you change it.Read How-toCheck and Accept ResultsHow to read a calculator's results, choose a passing member, and press Accept so the calculation moves into Project Outputs.Read How-toPay and Download Your DocumentsPay for accepted calculations on Project Outputs, or send the property owner a payment link, then download the Project Summary, Calculations and Drawings.Read TroubleshootingNo Member PassesWhat the "No member passes - change the inputs." notice means on the lintel and beam calculators, and which inputs to check first.Read Building & EngineeringWhat is "good ground" under NZS 3604?Good ground permanently takes 300 kPa ultimate bearing pressure, excluding compressible soils, expansive clays and ground that could move 25 mm or more.Read Building & EngineeringWhen do you need a structural engineer?You need a structural engineer when work falls outside NZS 3604 and the other Acceptable Solutions, so the structure must be specifically designed.Read