Worked example · CALC-008
How to Use the Raft Slab Reduced Bearing Single Storey Calculator: Worked Example
A step-by-step worked example of the Raft Slab Reduced Bearing Single Storey calculator, with a screen-recorded video - a raft slab for a single-storey house on 200 kPa ground, from Project Settings to the accepted calculation and its documents.
- Author
- ArchiSuite
- Technical review:
- Michael Sheridan
- Reviewed:
- Published:
On this page
This worked example takes one real design through the Raft Slab Reduced Bearing Single Storey calculator, from Project Settings to an accepted calculation in Project Outputs and the documents it produces. The calculator sizes the ribs of a raft slab for a single-storey house where the ground's ultimate bearing capacity is below the 300 kPa of NZS 3604 good ground: the external load-bearing rib under the outside walls, any internal load-bearing rib, and the internal non-load-bearing rib. It finds the rib width that keeps the ground pressure within that lower bearing capacity. Every value below was entered in ArchiSuite, and every result was read from it.
Video tutorial#
The example project#
The same single-storey house as the TC1 example, on ground with a 200 kPa ultimate bearing capacity: light roof trusses spanning 9 m with a 0.6 m eave, on 2.4 m external walls with light weatherboard cladding. There is no internal load-bearing wall, and the footing width is left for the calculator to choose.
What the example assumes:
The ground's ultimate bearing capacity is 200 kPa, from the site's geotechnical assessment. The house is the same as in the TC1 Single Storey Foundation worked example, so the two can be compared.
The trusses span the full width of the house, so there is no internal load-bearing wall, and no point load on the slab.
The values are an illustration. They are not defaults for your project.
Step 1: Check the project information#
The foundation calculators read one value from the active project's Project Settings:
| Project Setting | Value used | Unit | Why it matters here |
|---|---|---|---|
| Geotechnical Ultimate Bearing Capacity | 200 | kPa | The ground's ultimate bearing capacity, from the site's geotechnical assessment. The ribs are sized so the ground pressure stays within it. |
The only Project Setting the foundation calculators read. Select Foundations under What are you designing? in Project Settings to show it. Without it the calculation is refused when you click Analyse Data.
Step 2: Open the calculator#
Make the project active. Its name is shown under Active project at the top of every page.
Click All Calculators in the sidebar.
Under Foundations, choose Raft Slab Reduced Bearing Single Storey.
Click Add Raft Slab Single Storey Foundation, or New Raft Slab Single Storey Foundation once the project has one.
Step 3: Enter the foundation inputs#
Above the form, the arrangement drawing shows a section through the slab: the external rib under the wall, the roof span A (and B where an internal wall divides it), the wall height C and the eave D. The same letters are beside the input labels, and the drawing follows your inputs as you type.
These are the exact values entered in the recording:
| Section | Field | Value used | Unit | What it means |
|---|---|---|---|---|
| General Info | Calculation Name | FD3 - House on a raft slab | - | Names the calculation in Project Outputs and on the drawings and calculations. |
| Footing Width Preferences | Footing width | Auto | - | The calculator chooses the edge footing width. Manual lets you set it (200 mm or more). Auto is already selected on a new calculation. |
| Roof (External) | Roof loaded dimension | (left blank) | m | Left blank: the roof span and eave below give it instead (the calculator takes half the span plus the eave). |
| Roof (External) | Roof span, A or B | 9 | m | The span of the roof framing that bears on the external wall: here trusses spanning 9 m from wall to wall. With an internal load-bearing wall it is the larger bay (A or B on the drawing). |
| Roof (External) | Eave / overhang, D | 0.6 | m | The eave overhang beyond the external wall. |
| Roof (External) | Roof type | Light | - | Light roofing (for example long-run metal). |
| Wall (External) | Wall height, C | 2.4 | m | The height of the external timber-framed wall on the foundation (up to 4.8 m). |
| Wall (External) | Wall cladding type | Light | - | The cladding weight of that wall: light weatherboards here. |
A few points from the recording:
Give the roof one way only: the Roof loaded dimension, or the Roof span and Eave / overhang. With the span, the calculator takes half the span plus the eave as the roof width the external wall carries.
The Roof span is the span of the roof framing that bears on the wall. Here the trusses span the whole 9 m width. Where an internal load-bearing wall divides the roof, enter the larger bay.
Footing Width Preferences starts on Auto: the calculator chooses the width. Choose Manual to set it yourself (200 mm or more).
Internal Load-Bearing Wall Foundations and Point Loads are optional. Leave them empty when there is no internal load-bearing wall or point load, as here.
Back at the top of the page, the arrangement drawing now shows this house:
Step 4: Run the calculation#
Click Analyse Data. ArchiSuite reads the bearing capacity from Project Settings and designs the ribs. The Foundation Category Summary appears below the form. If an input is out of range, the form says so beside the field and does not submit.
Step 5: Understand the results#
The summary#
These are the values ArchiSuite showed for this example:
| Category | Footing Width, B (m) | Footing Depth, D (m) | Status |
|---|---|---|---|
| External Load-Bearing Rib/Wall | 0.200 | 0.305 | PASS |
| Internal Load-Bearing Rib/Wall | - | - | SKIPPED |
| Internal Non-Load-Bearing Floor/Rib | 0.100 | 0.305 | PASS |
What the rows mean:
External Load-Bearing Rib/Wall: the rib under the external walls, carrying the roof, the wall and its share of the slab. Footing Width, B is its width and Footing Depth, D its depth.
Internal Non-Load-Bearing Floor/Rib: the ribs across the slab that carry the slab and its floor load only. They are always designed.
Internal Load-Bearing Rib/Wall shows SKIPPED because no internal case was entered. With an internal load-bearing wall it is designed too.
Status must show PASS (or SKIPPED for a row with no inputs) before you can accept.
The checks#
The Structural Calculations work out the load on each rib per metre and check the ground pressure under it. Their design inputs set the limits from the bearing capacity: "Bearing limit, ULS 0.5 of ultimate" and "Bearing limit, SLS 1/3 of ultimate". Utilisation is demand ÷ capacity or limit; a utilisation of 1 or less passes.
| Part | Check | Demand | Capacity or limit | Utilisation |
|---|---|---|---|---|
| External rib | Ground bearing (G + 0.7Q) – governs | 33.3 kPa | 66.7 kPa | 0.50 |
| Non-load-bearing rib | Ground bearing (G + 0.7Q) – governs | 42.4 kPa | 66.7 kPa | 0.64 |
The document's conclusion:
What the checks show for this house:
On 200 kPa ground the service bearing limit is 66.7 kPa, a third of the 200 kPa entered, so the ground bearing under the service loads (G + 0.7Q) governs both ribs.
The external rib is 200 mm wide and at 0.50. In the calculation's words: "Common width. The external and internal load-bearing ribs take one width, the smallest at which every one of them passes." With Auto, the calculator chooses that width; with Manual you set it.
The non-load-bearing rib is at 0.64: it carries the slab and its floor load on 100 mm.
Step 6: Accept and access the documentation#
Check that every row shows PASS or SKIPPED, then click Accept in the summary header. ArchiSuite shows:
Open Project Outputs from the sidebar. The calculation is listed under Accepted calculator outputs included with its status.
What you can see and download, and when:
On screen. The arrangement drawing and the Foundation Category Summary are in the calculator itself as soon as you analyse.
The document packs. Project Outputs offers three PDFs: the Project Summary, the Structural Calculations (the design basis, the loads on each rib and the ground bearing checks) and the Structural Drawings. They download once every accepted output is paid.
Documents that wait for review. Where an Engineering Review is included (it always is for an account without a Licensed Building Practitioner number), the downloads also wait until ArchiSuite has reviewed the documents and released them for issue. See Pay and download your documents.
Once the review is released, the panel says so and every download opens.
The video ends with a quick look through the documents this example produced, as issued: the Project Summary; the PS1 Producer Statement - Design and its Schedule, shown unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; every page of the Structural Calculations; and every sheet of the Structural Drawings.
Common mistakes#
No bearing capacity in Project Settings. The calculation is refused. Select Foundations under What are you designing? in Project Settings, enter the Geotechnical Ultimate Bearing Capacity and click Update Project. See Project settings missing.
Entering the roof twice. Enter the roof loaded dimension, or the roof span and eave, not both.
The whole roof width as the span where an internal wall supports the roof. Enter the larger bay, and add the internal wall as an internal case.
Leaving out an internal load-bearing wall. If one carries the roof, add it under Internal Load-Bearing Wall Foundations; otherwise its rib is not designed.
The wrong calculator. This calculator is for ground with a bearing capacity below 300 kPa. On good ground use the TC1 calculator, and on TC2 land the TC2 one.
The same name twice. Each calculation in a project needs its own name. Change the Calculation Name.
Related guides#
Raft Slab Reduced Bearing Single Storey: every input, result and refusal of this calculator.
Open the calculator from All Calculators → Foundations (signed in).
The inputs explained: Geotechnical Ultimate Bearing Capacity, Footing width, Roof loaded dimension, Roof span, Roof type, Wall height and Wall cladding weight.
The other foundation worked examples: TC1 Single Storey Foundation, TC2 Single Storey Foundation and Square Pad Foundation.
Project Settings, Check and accept results and Pay and download your documents.
Engineering note#
Recorded with CALC-008 Raft Slab Reduced Bearing Single Storey version 1.17.0 on 2026-11-24.
Video transcript#
0:07 The project Worked Example - Raft Slab Single Storey Foundation is active. Under What are you designing?, Foundations is selected, and the calculator reads one Project Setting: the Geotechnical Ultimate Bearing Capacity, 200 kPa, below the 300 kPa of NZS 3604 good ground, which is why a raft slab is used.
0:18 Under All Calculators, in Foundations, open Raft Slab Reduced Bearing Single Storey, then Add Raft Slab Single Storey Foundation. It sizes the ribs of a raft slab for a single-storey house where the ground's bearing capacity is below 300 kPa.
0:33 The calculation is named FD3 - House on a raft slab. Footing Width Preferences is left on Auto, so the calculator chooses the width of the edge footing.
0:42 In External Load-Bearing Wall Foundations, the roof is entered by its span instead of its loaded dimension: light roof trusses spanning 9 m with a 0.6 m eave, on 2.4 m external walls with light cladding. There is no internal load-bearing wall, so the optional internal cases are left empty.
1:02 Back at the top of the page, the arrangement drawing has followed the inputs.
1:10 Analyse Data runs the calculation. When it finishes, the summary appears below the form.
1:17 The external load-bearing rib is 0.200 m wide and 0.305 m deep, and passes. The internal non-load-bearing rib is designed too; the internal load-bearing row is SKIPPED, because no internal case was entered.
1:29 Accept adds the calculation to Project Outputs.
1:34 Project Outputs lists FD3 - House on a raft slab as an accepted output. The Structural Calculations and Structural Drawings, with the full checks and the foundation details, download from here once the outputs are paid and, where Engineering Review is included, reviewed and released. Prices are hidden in this video.
1:46 After payment and Engineering Review (not shown), Project Outputs shows the document packs ready to download. A quick look through what they contain: the Project Summary, with the project and every accepted calculation; the PS1 Producer Statement - Design and its Schedule, shown here unsigned with the signatory withheld; the B2 durability letter and the Letter of Limited Review; the Structural Calculations; and the Structural Drawings.