Calculator guide · CALC-006

TC2 Single Storey Foundation

Size the rib widths and top and bottom bars of a stiffened pod-and-rib slab for a single-storey house, with ground-bearing and loss-of-support checks.

Video: a worked example

One real design taken through this calculator, from Project Settings to the issued documents. Read the worked example and transcript
On this page

TC2 Single Storey Foundation designs a stiffened pod-and-rib slab for a single-storey house. For the external load-bearing rib, the governing internal load-bearing rib and the internal non-load-bearing rib, it chooses a rib width and top and bottom reinforcing bars. It checks each rib for ground bearing and for loss of support: bending, shear and deflection if the ground stops supporting part of the rib. It uses the bearing capacity in your Project Settings.

TC2 Single Storey Foundation · CALC-006

Size foundation ribs and reinforcement for a single-storey TC2 slab, including loss-of-support checks.

Use it when

  • A single-storey house requiring a TC2 slab design.
  • Your geotechnical assessment confirms this foundation type suits the site.

Results

  • External and internal rib widths.
  • Top and bottom rib reinforcement.
  • Ground-bearing and loss-of-support checks.

Limits

  • Single storey only.
  • No separate point-load or pad design.
  • Steel-fibre slab details are not suitable for polished or exposed concrete floors.

Before you start#

  • Set the bearing capacity in Project Settings. Open Project Settings and enter Geotechnical Ultimate Bearing Capacity (150 to 300 kPa), then click Update Project. It is the only Project Settings value this calculator reads, and it is not on the form. If Foundations is the only box ticked under What are you designing?, this is the only site parameter the settings form asks for.

  • Confirm your ground information first. ArchiSuite does not work out whether your land is TC2 or its bearing capacity, and the calculator does not check the technical category. The only ground value it reads is the bearing capacity in Project Settings.

  • Polished floors. The TC2 drawing notes specify steel-fibre-reinforced concrete for the ribs, and say steel fibre-reinforced slabs must not be used for polished or exposed concrete surfaces. Talk to your designer first if you want a polished floor.

  • Point loads. There is no point-load input, and the foundation calculation does not assess concentrated loads. An Important Design Limitation notice says so before the form opens. The TC2 drawing allows an incidental point load of up to 10 kN (ULS) on the point load strip it details. A larger concentrated load needs specific engineering design.

  • Measure from your plans:

    • For the external wall line: the roof loaded dimension, or the roof span and eave / overhang, plus the roof type, the wall height and the cladding type.

    • For each internal load-bearing wall line: its roof loaded dimension, roof type, wall height and cladding type.

The TC2 Single Storey form

Step by step#

  1. Click All Calculators in the sidebar, choose the Foundations tab and click TC2 Single Storey Foundation.

  2. Click New TC2 Single Storey Foundation (or Add TC2 Single Storey Foundation if the list is empty).

  3. Under General Info, enter a Calculation Name.

  4. Under External Load-Bearing Wall Foundations, fill in Roof (External): enter Roof loaded dimension (m), or both Roof span (m) and Eave / overhang (m). Then choose Roof type.

  5. Fill in Wall (External): enter Wall height (m) and choose Wall cladding type.

  6. Optional: under Internal Load-Bearing Wall Foundations (Optional), click Add Internal Foundation (or Add Case). Add up to five cases. In each Case:

    • Under Roof (Internal), enter Roof loaded dimension (m) and choose Roof type.

    • Under Wall (Internal), enter Wall height (m) and choose Wall cladding type.

  7. Click Analyse Data. The results appear under Foundation Category Summary.

  8. Check each row's status, then click Accept. The button changes to Accepted, and the calculation is added to Project Outputs.

  9. To change it later, open it from the list, edit the inputs and click Update Analysis.

Rib widths, depth and status

The inputs#

Roof (External) and Wall (External)#

These describe the external wall line. The form's note says: "Enter either the roof loaded dimension, or both the roof span and eave / overhang. Use the largest roof loaded dimension supported by an external wall."

Internal Load-Bearing Wall Foundations#

Add one case per internal load-bearing wall line (Internal group). The form says: "Enter roof loaded dimension on load-bearing wall." Internal cases take the roof loaded dimension only. Each case is designed, and the results show the governing case: the widest, then the one with the most reinforcement. With no cases, the internal row shows SKIPPED. The non-load-bearing rib is always designed, and you enter nothing for it.

The grey "Medium" in an internal Wall cladding type box is only a placeholder, so pick a value.

  • Roof loaded dimension, L.D (m)Optional

    External walls and roof

    m

  • Roof span, Sr (m)Optional

    External walls and roof

    m

  • Eave / overhang, Se (m)Optional

    External walls and roof

    m

  • Roof typeOptional

    External walls and roof

    As shown on the form

  • Wall height (m)Optional

    External walls and roof

    m

  • Wall typeOptional

    External walls and roof

    As shown on the form

  • Roof loaded dimension, L.D (m)Optional

    Internal load-bearing ribs

    m

  • Roof span, Sr (m)Optional

    Internal load-bearing ribs

    m

  • Eave / overhang, Se (m)Optional

    Internal load-bearing ribs

    m

  • Roof typeOptional

    Internal load-bearing ribs

    As shown on the form

  • Wall height (m)Optional

    Internal load-bearing ribs

    m

  • Wall typeOptional

    Internal load-bearing ribs

    As shown on the form

Read from TC2 Single Storey Foundation (CALC-006, version 1.19.0) as it runs today. The form may also show its own limit beside an input.

Worked example#

This is a representative example from ArchiSuite's test suite, not a design for your site. Project Settings bearing capacity: 250 kPa.

SectionInputValue
Roof (External)Roof span / Eave / overhang7.0 m / 0.45 m
Roof (External)Roof typeLight
Wall (External)Wall height / Wall cladding type2.4 m / Light
Case 1Roof loaded dimension / Roof type2.5 m / Heavy
Case 1Wall height / Wall cladding type2.4 m / Light

After Analyse Data, all three rows show PASS with a depth of 0.305 m. The bars chosen for each rib appear in the PDFs and drawings.

Results#

The Foundation Category Summary lists External Load-Bearing Rib/Wall, Internal Load-Bearing Rib/Wall and Internal Non-Load-Bearing Floor/Rib. Each row has these columns:

  • Footing Width, B (m)

  • Footing Depth, D (m): always 0.305 m.

  • Status:

    • PASS: the rib passes every check.

    • FAIL

    • SKIPPED: no internal cases were entered.

For each rib, the calculator works up through widths and bar sets and stops at the first combination that passes every check:

  • Widths. Load-bearing ribs are tried from 0.300 to 0.500 m and the non-load-bearing rib from 0.100 to 0.200 m, in 0.05 m steps.

  • Bars. For each width it tries top and bottom bar sets from 2HD12 up to 4HD20 for load-bearing ribs, or one HD12, HD16 or HD20 bar for the non-load-bearing rib.

  • Checks.

    • ground bearing for four load combinations

    • deflection over a 4.0 m simply supported span and a 2.0 m cantilever, which must stay below span/400

    • bending

    • shear

  • FAIL. If nothing passes, the row shows FAIL with the last combination tried.

The reinforcement is not shown on screen. After paying, you can download:

  • "TC2 Foundation Structural Calculations (Single Storey)": the load build-up, the bearing table and the "Loss-of-support design strips" checks for each rib. The internal rib's heading notes "Critical case displayed only".

  • The summary PDF.

  • The drawings: a rib schedule with widths, top and bottom steel, and steel-fibre notes. See Pay and download.

Limitations#

  • Single storey only. Each line is a roof plus one wall. For two storeys, use TC2 Multi Storey Foundation.

  • No point loads or pads. If posts or beams bear on the slab, raise a design request or ask your engineer (see When no calculator fits).

  • Fixed ranges. Rib widths are 300 to 500 mm for load-bearing ribs and 100 to 200 mm for the non-load-bearing rib. The depth is fixed at 305 mm, and the bar sets are limited to those above.

  • Polished floors. The drawing notes say a steel fibre-reinforced slab must not be used for polished or exposed concrete surfaces.

  • Number of cases. You can enter up to five internal cases.

  • Bearing capacity. The Project Settings bearing capacity must be from 150 to 300 kPa.

  • Site category. The calculator does not assess technical category, settlement or liquefaction.

Common errors and how to fix them#

  • "Project Settings geotechnical ultimate bearing capacity is required before running this calculation." Enter it in Project Settings, click Update Project, and analyse again. See Project settings missing.

  • "Project Settings geotechnical ultimate bearing capacity must be between 150 and 300 kPa." Correct the value in Project Settings.

  • "Calculation name is required": enter a Calculation Name.

  • "roof_type must be one of: light, heavy." Choose Roof type for the external roof and every case.

  • "roof span must be a number." Enter the roof as a loaded dimension, or as span plus eave / overhang.

  • "eave width must be a number." You entered a span without an eave / overhang.

  • "upper wall_type must be one of: light, medium, heavy." Choose Wall cladding type. On this form, "upper wall" means the Wall (External) / Wall (Internal) inputs.

  • "upper wall height must be a number." Enter Wall height (m).

  • "Enter either the roof loaded dimension or the roof span and eaves width, not both." Clear one of the two ways.

  • "Allowed range: ..." under a box: the value is outside what the calculator accepts.

  • A FAIL row: check that line's inputs first. If they are right, the line is outside what this calculator can design. See When no calculator fits.

  • "This calculation cannot be accepted or issued. ...": the rest of the message gives the reason. See Check and accept results.

  • "Permission denied": only admins and editors can update or delete a saved calculation.

Worked example

Was this helpful?