Calculator guide · CALC-008

Raft Slab Reduced Bearing Single Storey

Size one common footing width for the load-bearing ribs of a pod-and-rib slab on reduced-bearing ground, for a single-storey house, plus pads for up to five point loads.

Video: a worked example

One real design taken through this calculator, from Project Settings to the issued documents. Read the worked example and transcript
On this page

Raft Slab Reduced Bearing Single Storey designs ArchiSuite's own pod-and-rib slab for a single-storey house where reduced ground bearing is the concern. It uses the same detail sheets as the TC1 calculator. The calculator finds one common footing width for the external rib and every internal load-bearing rib, or checks a width you set. It also sizes the internal non-load-bearing rib, and can design a square pad under each of up to five point loads. Ground bearing is checked against the bearing capacity in your Project Settings.

Raft Slab for Reduced Ground Bearing - Single Storey · CALC-008

Size pod-and-rib slab foundations for reduced ground bearing, with one common load-bearing rib width and pads for up to five point loads.

Use it when

  • A single-storey house on ground with ultimate bearing capacity from 150 kPa to below 300 kPa.
  • Your geotechnical assessment confirms this foundation type suits the site.

Results

  • A common width for load-bearing ribs.
  • Non-load-bearing rib widths.
  • Pad sizes and reinforcement for entered point loads.

Limits

  • Single storey only.
  • ArchiSuite slab details only; not a proprietary raft-system design.
  • General rib reinforcement, settlement and liquefaction are not assessed.
  • No earthquake reactions at pads.

Before you start#

  • Set the bearing capacity in Project Settings. Open Project Settings and enter Geotechnical Ultimate Bearing Capacity (150 to 300 kPa), then click Update Project. Use the value from your geotechnical information. It is the only Project Settings value this calculator reads, and it is not on the form. If Foundations is the only box ticked under What are you designing?, this is the only site parameter the settings form asks for.

  • Check the slab type suits the site. The calculator uses only the bearing capacity number. It does not check settlement or liquefaction, and it is not a design for a proprietary (branded) raft or pod system. See Raft slab for reduced ground bearing.

  • Optional: add your geotechnical report details under Geotechnical Properties (optional). They are printed on the drawings.

  • Measure from your plans:

    • For the external wall line: the roof loaded dimension, or the roof span and eave / overhang, plus the roof type, the wall height and the cladding type.

    • For each internal load-bearing line: its roof loaded dimension, roof type, wall height and cladding type.

    • For each post or beam bearing on the slab: its four factored reactions in kN.

    • If you want to check a width already on your drawings, note that width in mm.

The Raft Slab Single Storey form

Step by step#

  1. Click All Calculators in the sidebar, choose the Foundations tab and click Raft Slab Reduced Bearing Single Storey.

  2. Click New Raft Slab Single Storey (or Add Raft Slab Single Storey Foundation if the list is empty).

  3. Under General Info, enter a Calculation Name.

  4. Under Footing Width Preferences, choose Auto to let the calculator find the width. Or choose Manual and enter Footing width (mm), at least 200.

  5. Under External Load-Bearing Wall Foundations, fill in Roof (External): enter Roof loaded dimension (m), or both Roof span (m) and Eave / overhang (m). Check Roof type, which starts at Light.

  6. Fill in Wall (External): enter Wall height (m) and check Wall cladding type, which starts at Medium.

  7. Optional: under Internal Load-Bearing Wall Foundations (Optional), click Add Internal Foundation (or Add Case), up to five. In each Case:

    • Under Roof (Internal), enter Roof loaded dimension (m) and Roof type.

    • Under Wall (Internal), enter Wall height (m) and Wall cladding type.

  8. Optional: under Concentrated Point Loads (Optional), click Add Concentrated Load (or Add Load), up to five. Fill in:

    • Name / reference

    • On thickening?

    • 1.35G (kN)

    • 1.2G + 1.5Q (kN)

    • 1.2G + W + ψcQ (kN)

    • 0.9G + W uplift (kN)

  9. Click Analyse Data. The results appear under Foundation Category Summary.

  10. Check each row's status, then click Accept. The button changes to Accepted, and the calculation is added to Project Outputs.

  11. To change it later, open it from the list, edit the inputs and click Update Analysis.

Results and the Accept button

The inputs#

Footing Width Preferences#

The form's note says: "Select your preferred load-bearing footing width, or select Auto to calculate the most efficient footing width." (Footing width mode)

  • Auto tries one common width for all load-bearing ribs: 200, 250, 300, 350, 400, 450 and 500 mm. It stops at the first width where the external rib and every internal case pass.

  • Manual checks only the width you enter. It must be at least 200 mm, and the box is greyed out unless Manual is selected.

The non-load-bearing rib is sized separately, from 100 to 300 mm, either way.

Roof (External) and Wall (External)#

These describe the external wall line. The form's note says: "Enter either the roof loaded dimension, or both the roof span and eave / overhang. Use the largest roof loaded dimension supported by an external wall."

Internal Load-Bearing Wall Foundations#

Add one case per internal load-bearing wall line (Internal group). The form says: "Enter roof loaded dimension on load-bearing wall." Every case is checked at the common width, and the results show the governing case. With no cases, the internal row shows SKIPPED. In an internal Wall cladding type box, a grey "Medium" is only a placeholder, so pick a value.

Concentrated Point Loads#

The form's note says: "Configure up to 5 concentrated point load design actions. Reaction inputs must be negative for downward forces, and positive for uplift." (Point loads)

  • 1.35G, 1.2G + 1.5Q and 1.2G + W + ψcQ are negative.

  • 0.9G + W uplift is zero or positive.

  • Every point load is designed as a square pad.

  • On thickening? Yes means the load sits over a slab thickening (a deeper strip of concrete, such as the rib along the slab's outside edge). The calculator then also checks that thickening as an edge beam, using the common footing width it selected. New point loads start at Yes.

  • Footing Width Mode / Footing Width, b (mm)Optional

    mm

  • Roof loaded dimension, L.D (m)Optional

    External walls and roof

    m

  • Roof span, Sr (m)Optional

    External walls and roof

    m

  • Eave / overhang, Se (m)Optional

    External walls and roof

    m

  • Roof typeOptional

    External walls and roof

    As shown on the form

  • Wall height (m)Optional

    External walls and roof

    m

  • Wall typeOptional

    External walls and roof

    As shown on the form

  • Roof loaded dimension, L.D (m)Optional

    Internal load-bearing ribs

    m

  • Roof span, Sr (m)Optional

    Internal load-bearing ribs

    m

  • Eave / overhang, Se (m)Optional

    Internal load-bearing ribs

    m

  • Roof typeOptional

    Internal load-bearing ribs

    As shown on the form

  • Wall height (m)Optional

    Internal load-bearing ribs

    m

  • Wall typeOptional

    Internal load-bearing ribs

    As shown on the form

  • On thickening?Optional

    Point loads

    As shown on the form

  • 1.35G (kN)Optional

    Point loads

    As shown on the form

  • 1.2G + 1.5Q (kN)Optional

    Point loads

    As shown on the form

  • 1.2G + W + ψcQ (kN)Optional

    Point loads

    As shown on the form

  • 0.9G + W uplift (kN)Optional

    Point loads

    As shown on the form

Read from Raft Slab for Reduced Ground Bearing - Single Storey (CALC-008, version 1.17.0) as it runs today. The form may also show its own limit beside an input.

Worked example#

This is a representative example from ArchiSuite's test suite, not a design for your site. Project Settings bearing capacity: 250 kPa. Footing width mode: Auto.

SectionInputValue
Roof (External)Roof span / Eave / overhang7.0 m / 0.45 m
Roof (External)Roof typeLight
Wall (External)Wall height / Wall cladding type2.4 m / Light
Case 1Roof loaded dimension / Roof type2.5 m / Heavy
Case 1Wall height / Wall cladding type2.4 m / Light
Point Load 1Name / On thickening?PL1 / No
Point Load 11.35G / 1.2G + 1.5Q / 1.2G + W + ψcQ / 0.9G + W uplift-20 / -25 / -15 / 3 kN

After Analyse Data, all three rows show PASS:

  • The external and internal load-bearing ribs share the first Auto width, 0.200 m.

  • The non-load-bearing rib is 0.100 m.

  • Every row has a depth of 0.305 m.

PL1's pad is in the PDFs.

Results#

The Foundation Category Summary lists External Load-Bearing Rib/Wall, Internal Load-Bearing Rib/Wall and Internal Non-Load-Bearing Floor/Rib. Each row has these columns:

  • Footing Width, B (m): the external and internal rows always show the same common width.

  • Footing Depth, D (m): always 0.305 m.

  • Status:

    • PASS

    • FAIL: the rib does not pass at the width shown. In Auto, if no width up to 500 mm works, the rows show 500 mm.

    • SKIPPED

Rib reinforcement is not sized.

Point-load results are not shown on screen. After paying, you can download:

  • "Raft Slab for Reduced Ground Bearing Calculations Single Storey": loads, load combinations and bearing checks for each rib. The internal heading notes "Critical case displayed only". It also has the pad and edge-beam checks for point loads. A pad with no solution reads "SED required" (specific engineering design).

  • The summary PDF.

  • The drawings: the TC1 detail sheets with your values. See Pay and download.

Limitations#

  • Single storey only. For two storeys, use Raft Slab Reduced Bearing Double Storey.

  • One common width.

    • All load-bearing ribs get the same width.

    • Auto searches 200 to 500 mm, and Manual must be at least 200 mm.

    • Non-load-bearing ribs are 100 to 300 mm.

    • The rib depth is fixed at 305 mm.

  • No reinforcement design. General rib reinforcement is not sized.

  • Bearing capacity number only. There are no settlement or liquefaction checks. The Project Settings value must be from 150 to 300 kPa.

  • ArchiSuite's slab detail only. It is not a proprietary raft or pod system design.

  • Pads:

    • square, 300 to 3000 mm wide and 300 to 500 mm thick, with HD12, HD16 or HD20 bottom bars

    • no earthquake reactions or column base moments

    • punching shear assumes a 90 x 90 mm post

  • Number of entries. Up to five internal cases and five point loads.

Common errors and how to fix them#

  • "Project Settings geotechnical ultimate bearing capacity is required before running this calculation." Enter it in Project Settings, click Update Project, and analyse again. See Project settings missing.

  • "Project Settings geotechnical ultimate bearing capacity must be between 150 and 300 kPa." None of the foundation calculators run below 150 kPa.

  • "Required when Manual selected" / "Min 200 mm": enter a Footing width (mm) of at least 200, or switch to Auto.

  • "footing_width_b_mm must be at least 200 mm." The same check, made when the calculation runs.

  • "Calculation name is required": enter a Calculation Name.

  • "roof_type must be one of: light, heavy." Choose Roof type for every internal case.

  • "roof span must be a number." / "eave width must be a number." Enter the roof as a loaded dimension, or as span plus eave / overhang.

  • "upper wall_type must be one of: light, medium, heavy." Choose Wall cladding type. "Upper wall" means the Wall (External) / Wall (Internal) inputs.

  • "upper wall height must be a number." Enter Wall height (m).

  • "Enter either the roof loaded dimension or the roof span and eaves width, not both." Clear one of the two ways.

  • "Must be strictly negative (< 0)" / "Must be >= 0" / "Required" on a point load: downward reactions are negative, uplift is zero or positive, and every reaction must be filled in.

  • Analyse Data does nothing: a point load has no Name / reference.

  • A FAIL row:

    • In Manual, only your width is checked. Switch to Auto to let the calculator search 200 to 500 mm.

    • In Auto, check that line's inputs. If they are right, the slab is outside what this calculator can design. See When no calculator fits.

  • "This calculation cannot be accepted or issued. ...": the rest of the message gives the reason. See Check and accept results.

  • "Permission denied": only admins and editors can update or delete a saved calculation.